Yaskawa CIMR-PU2A0040 [315/548] Motor does not rotate properly after pressing run button or after entering external run command

Yaskawa CIMR-PU2A0040 [315/548] Motor does not rotate properly after pressing run button or after entering external run command
Cause Possible Solutions
The wrong password was entered.
If the password entered to A1-04 does not match the password saved to A1-05, then drive
settings cannot be changed.
Reset the password.
If you cannot remember the password:
Scroll to A1-04. Press
STOP
and simultaneously. Parameter A1-05 will appear.
Set a new password to parameter A1-05.
Undervoltage was detected.
Check the drive input power voltage by looking at the DC bus voltage (U1-07).
Check all main circuit wiring.
u
Motor Does Not Rotate Properly after Pressing RUN Button or after Entering External
Run Command
n
Motor Does Not Rotate
Cause Possible Solutions
The drive is not in the Drive Mode.
Check if the DRV light on the digital operator is lit.
Enter the Drive Mode to begin operating the
motor. Refer to The Drive, Programming, and Clock Adjustment
Modes on page 106.
was pushed.
Stop the drive and check if the correct frequency reference source is selected. If the operator keypad shall be the
source, the LO/RE button LED must be on. If the source is REMOTE, it must be off.
Take the following steps to solve the problem:
Push .
If o2-01 is set to 0, then the LO/RE button will be disabled.
Auto-Tuning has just completed.
When Auto-Tuning completes, the drive is switched back to the Programming Mode. The Run command will
not be accepted unless the drive is in the Drive Mode.
Use the digital operator to enter the Drive Mode. Refer to The Drive, Programming, and Clock Adjustment
Modes on page 106.
A Fast Stop was executed and has
not yet been reset.
Reset the Fast Stop command.
Settings are incorrect for the source
that provides the Run command.
Check parameter b1-02 (Run Command Selection).
Set b1-02 so that it corresponds with the correct Run command source.
0: Digital operator
1: Control circuit terminal (default setting)
2: MEMOBUS/Modbus communications
3: Option card
There is faulty wiring in the control
circuit terminals.
Check the wiring for the control terminal.
Correct wiring mistakes.
Check the input terminal status monitor (U1-10).
The drive has been set to accept the
frequency reference from the
incorrect source.
Check parameter b1-01 (Frequency Reference Selection 1).
Set b1-01 to the correct source of the frequency reference.
0: Digital operator
1: Control circuit terminal (default setting)
2: MEMOBUS/Modbus communications
3: Option card
4: Pulse train input (RP)
The terminal set to accept the main
speed reference is set to the incorrect
voltage and/or current.
Refer to Terminals A1, A2, and A3 Input Signal Selection on page 93.
Selection for the sink/source mode
and the internal/external power
supply is incorrect.
Check jumper S3. Refer to Sinking/Sourcing Mode Switch for Digital Inputs on page 92.
Frequency reference is too low.
Check the frequency reference monitor (U1-01).
Increase the frequency by changing the maximum output frequency (E1-09).
Multi-function analog input is set up
to accept gain for the frequency
reference, but no voltage (current)
has been provided.
Check the multi-function analog input settings.
Check if analog input A1, A2, or A3 is set for frequency reference gain (H3-02, H3-10, H3-06 = 1). If so, check
if the correct signal is applied to the terminal. The gain and the frequency reference will be 0 if no signal is
applied to the gain input.
Check if H3-02, H3-10, and H3-06 have been set to the proper values.
Check if the analog input value has been set properly. (U1-13 to U1-15)
6.10 Troubleshooting without Fault Display
YASKAWA SIEP YAIP1U 01A AC Drive - P1000 Technical Manual
315
6
Troubleshooting

Содержание

Скачать