EWWP014~065KBW1N
Packaged water-cooled water chillers
4PW61659-1 – 07.2010
Installation manual
3
■ Additional water piping delivered with the unit
All additional water piping must be installed on the system according
to the piping diagram as mentioned in the operation manual. The
flowswitch must be connected as described on the wiring diagram.
See also chapter "Before starting" on page 4.
1 The flowswitch must be installed in the water outlet pipe of the
evaporator to prevent the unit from operating at a water flow
which is too low.
A terminal (X65A) is provided in the switch box for the electrical
connection of the flowswitch (S10L).
2 Shut-off valves must be installed at the unit so that normal
servicing of the water filter can be accomplished without
draining the complete system.
3 Air purge valves must be provided at all high points of the
system. The vents should be located at points which are easily
accessible for servicing.
4 The water filter must be installed in front of the unit for removing
dirt from the water to prevent damage to the unit or blockage of
the evaporator or condenser. The water filter must be cleaned on
a regular base.
WATER QUALITY SPECIFICATIONS
A = corrosion B = scale
CONNECTING THE WATER CIRCUIT
The evaporator and condenser are foreseen of GAS male pipe thread
for the water inlet and outlet (refer to the outlook diagram). Evaporator
and condenser water connections are to be made in accordance with
the outlook diagram, respecting the water in- and outlet.
If air, moisture or dust gets in the water circuit, problems may occur.
Therefore, always take into account the following when connecting
the water circuit:
1 Use clean pipes only.
2 Hold the pipe end downwards when removing burrs.
3 Cover the pipe end when inserting it through a wall so that no dust
and dirt enter.
WATER CHARGE, FLOW AND QUALITY
To assure proper operation of the unit a minimum water volume is
required in the system and the water flow through the evaporator
must be within the operation range as specified in the table below.
Carton box 1 water piping evaporator
2x Ball valve
1x Water filter
1x Air purge
1x T-joint for air purge
2x Flowswitch pipe
1x Flowswitch
+
1x T-joint
Carton box 2 water piping condenser
2x Ball valve
1x Water filter
1x Air purge
1x T-joint for air purge
It is very important to install the flowswitch as shown in the
figure. Observe the position of the flowswitch in relation to
the direction of the water flow. If the flowswitch is mounted
in an other position, the unit is not protected properly
against freezing.
evaporator water condenser water
circulating
water
supply
water
circulating
water
supply
water
tendency
if out of
criteria
[<20°C] [20°C~60°C]
Items to be controlled
pH at 25°C
6.8~8.0 6.8~8.0 7.0~8.0 7.0~8.0 A + B
Electrical
conductivity
[mS/m]
at 25°C
<40 <30 <30 <30 A + B
Chloride ion
[mg Cl
–
/l]
<50 <50 <50 <50 A
Sulfate ion
[mg SO
4
2–
/l]
<50 <50 <50 <50 A
M-alkalinity
(pH 4.8)
[mg CaCO
3
/l]
<50 <50 <50 <50 B
Total hardness
[mg CaCO
3
/l]
<70 <70 <70 <70 B
Calcium
hardness
[mg CaCO
3
/l]
<50 <50 <50 <50 B
Silica ion
[mg SiO
2
/l]
<30 <30 <30 <30 B
Items to be referred to
Iron [mg Fe/l]
<1.0 <0.3 <1.0 <0.3 A + B
Copper [mg Cu/l]
<1.0 <0.1 <1.0 <0.1 A
Sulfide ion
[mg S
2–
/l]
not detectable A
Ammonium ion
[mg NH
4
+
/l]
<1.0 <0.1 <0.3 <0.1 A
Remaining
chloride
[mg Cl/l]
<0.3 <0.3 <0.25 <0.3 A
Free carbide
[mg CO
2
/l]
<4.0 <4.0 <0.4 <4.0 A
Stability index
————A + B
■ Use a good thread sealant for the sealing of the
connections. The sealing must be able to withstand the
pressures and temperatures of the system, it must also
be resistant to the used glycol in the water.
■ The exterior of the water pipes must be adequately
protected against corrosion.
Minimum
water volume (l)
Minimum
water flow
Maximum
water flow
EWWP014 62 19 l/min 75 l/min
EWWP022 103 31 l/min 123 l/min
EWWP028 134 40 l/min 161 l/min
EWWP035 155 47 l/min 186 l/min
EWWP045 205 62 l/min 247 l/min
EWWP055 268 80 l/min 321 l/min
EWWP065 311 93 l/min 373 l/min
Содержание
- Installation manual 1
- Packaged water cooled water chillers 1
- Daikin europe n v 2
- En60335 2 40 2
- Ewwp014kbw1n ewwp022kbw1n ewwp028kbw1n ewwp035kbw1n ewwp045kbw1n ewwp055kbw1n ewwp065kbw1n 2
- Jean pierre beuselinck general manager ostend 1st of july 2010 2
- Machinery 2006 42 ec electromagnetic compatibility 2004 108 ec 2
- Pw61842 3 2
- Electrical specifications 3
- Electrical specification 3
- Features 3
- Installation manual 3
- Introduction 3
- Options 3
- Options and feature 3
- Options and features 3
- Technical specifications 3
- Technical specification 3
- Ain component 4
- Checking the water circuit 4
- Election of location 4
- Hecking the water circuit 4
- Important information regarding the refrigerant used 4
- Inspecting and handling the unit 4
- Main components 4
- Mportant information regarding the refrigerant used 4
- Npacking and placing the unit 4
- Nspecting and handling the unit 4
- Operation range 4
- Peration range 4
- Selection of location 4
- Unpacking and placing the unit 4
- A terminal x65a is provided in the switch box for the electrical connection of the flowswitch s10l 5
- Air purge valves must be provided at all high points of the system the vents should be located at points which are easily accessible for servicing 5
- All additional water piping must be installed on the system according to the piping diagram as mentioned in the operation manual the flowswitch must be connected as described on the wiring diagram see also chapter before starting on page 4 5
- Ater charg 5
- Ater quality specifications 5
- Connecting the water circuit 5
- Flow and quality 5
- If air moisture or dust gets in the water circuit problems may occur therefore always take into account the following when connecting the water circuit 5
- It is very important to install the flowswitch as shown in the figure observe the position of the flowswitch in relation to the direction of the water flow if the flowswitch is mounted in an other position the unit is not protected properly against freezing 5
- Onnecting the water circuit 5
- Shut off valves must be installed at the unit so that normal servicing of the water filter can be accomplished without draining the complete system 5
- The water filter must be installed in front of the unit for removing dirt from the water to prevent damage to the unit or blockage of the evaporator or condenser the water filter must be cleaned on a regular base 5
- The flowswitch must be installed in the water outlet pipe of the evaporator to prevent the unit from operating at a water flow which is too low 5
- To assure proper operation of the unit a minimum water volume is required in the system and the water flow through the evaporator must be within the operation range as specified in the table below 5
- Water charge flow and quality 5
- Water quality specifications 5
- Before starting 6
- Connection of the water cooled water chiller power supply 6
- Efore starting 6
- Field wiring 6
- Ield wiring 6
- Interconnection cables 6
- Iping insulation 6
- Parts table 6
- Piping insulation 6
- Point for attention regarding quality of the public electric power supply 6
- Power circuit and cable requirements 6
- After installation and connection of the packaged water cooled water chiller the complete system must be checked and tested as described in checks before initial start up in the operation manual supplied with the unit 7
- Fill out the brief operation instructions form and fix it visibly near the operating site of the refrigeration system 7
- How to continue 7
- I do confirm having executed and checked all the above mentioned items 7
- Keep for future reference 7
- Ow to continue 7
- Brief operation instructions ewwp kb packaged water cooled water chiller 11
- Quipment technical data 11
- Up and shut down 11
Похожие устройства
- Daikin EWWP028KBW1N Инструкция по эксплуатации
- Daikin EWWP035KBW1N Инструкция по монтажу
- Daikin EWWP035KBW1N Инструкция по эксплуатации
- Daikin EWWP045KBW1N Инструкция по монтажу
- Daikin EWWP045KBW1N Инструкция по эксплуатации
- Daikin EWWP055KBW1N Инструкция по монтажу
- Daikin EWWP055KBW1N Инструкция по эксплуатации
- Daikin EWWP065KBW1N Инструкция по монтажу
- Daikin EWWP065KBW1N Инструкция по эксплуатации
- Daikin EWAD390D-SS Инструкция по монтажу
- Daikin EWAD440D-SS Инструкция по монтажу
- Daikin EWAD470D-SS Инструкция по монтажу
- Daikin EWAD510D-SS Инструкция по монтажу
- Daikin EWAD530D-SS Инструкция по монтажу
- Daikin EWAD560D-SS Инструкция по монтажу
- Daikin EWAD580D-SS Инструкция по монтажу
- Miniland HUMITOP Инструкция
- Miniland HUMITOP Чистящий лист
- Daikin EWAD180D-SL Инструкция по монтажу
- Daikin EWAD180D-SR Инструкция по монтажу