Step n. Leader Comp. Lag 1 Comp. Lag 2 Comp. Lag 3 Comp.
0 100% 100% 100% 100%
1 Fixed at 100% Fixed at 100% Fixed at 100% Unload up to 75%
2 Fixed at 100% Fixed at 100% Unload up to 75% Fixed at 75%
3 Fixed at 100% Unload up to 75% Fixed at 75% Fixed at 75%
4 Unload up to 75% Fixed at 75% Fixed at 75% Fixed at 75%
5 Fixed at 75% Fixed at 75% Fixed at 75% Unload up to 50%
6 Fixed at 75% Fixed at 75% Unload up to 50% Fixed at 50%
7 Fixed at 75% Fixed at 75% Fixed at 50% Unload up to 25%
8 If T is approaching SetP – Waiting
8a (T in reg band) Fixed at 75% Fixed at 75% Load up to 75% Stop
8b (T no in reg band) Fixed at 75% Fixed at 75% Fixed at 75% Stop
9(if lag2 at 75%) Fixed at 75% Fixed at 75% Fixed at 75% Off
10 Fixed at 75% Unload up to 50% Fixed at 50% Off
11 Fixed at 75% Fixed at 50% Fixed at 25% Off
12 If T is approaching SetP – Wait …..
13a (T in reg band) Fixed at 75% Load up to 75% Stop Off
13b (T out of reg band) Fixed at 75% Fixed at 50% Stop Off
14( lag1 at 75%) Fixed at 75% Unload up to 50% Off Off
15 Unload up to 50% Fixed at 50% Off Off
16 Fixed at 50% Unload up to 25% Off Off
17 If T is approaching SetP – Waiting
18a (T in reg band) Load up to 75% Stop Off Off
18b (T out of reg band) Fixed at 50% Stop Off Off
19 Unload up to 25% Off Off Off
20 If T is approaching SetP – Waiting
21
If (SetP - T) < Shutdown DT & Cooling
or (T – SetP) < Shutdown DT & Heating
Wait
22 Stop Off Off Off
23 Off Off Off Off