4. Controller Input/Output
The software refers to the configuration of the input and output channels of the controller as shown below.
4.1 Air-cooled chillers (Unit config. 00)
Digital inputs
Analogue inputs
N COMPRESSOR 1 COMPRESSOR 2 COMPRESSOR 3 COMPRESSOR 4
1 Evaporator inlet water
temperature
2 Evaporator water outlet
temperature (or common
evap outlet temp for units
with 2 evaporators)
Evaporator 1 water outlet
temperature
Evaporator 2 water outlet
temperature (for units with
2 evaporators)
3 Setpoint change Demand limit
4 Compressor discharge
temperature
Compressor discharge
temperature
Compressor discharge
temperature
Compressor discharge
temperature
5 Outside ambient
temperature
6 Compressor load Compressor load Compressor load Compressor load
7 Condensation pressure Condensation pressure Condensation pressure Condensation pressure
8 Oil pressure Oil pressure Oil pressure Oil pressure
N COMPRESSOR 1 COMPRESSOR 2 COMPRESSOR 3 COMPRESSOR 4
1 Compressor On/Off Compressor On/Off Compressor On/Off Compressor On/Off
2 Evaporator flow switch
3 Unit On/Off
4 High discharge temperature High discharge
temperature
High discharge
temperature
High discharge
temperature
5 Low pressure switch Low pressure switch Low pressure switch Low pressure switch
6 External alarm
7 Phase monitor (unit or
comp. #1)
Comp. #2 phase monitor Comp. #3 phase monitor Comp. #4 phase monitor
8 Enable double setpoint
9
10 Failed transition start Failed transition start Failed transition start Failed transition start
11 High pressure switch High pressure switch High pressure switch High pressure switch
12 Compressor overload Compressor overload Compressor overload Compressor overload