Working time for Sunday
18 days for forced off
Enter new password
5.5 Setting Menu
In this section, it is possible to set and display the setpoint values:
Cooling Setpoint (°C)
Active setpoint (if the function “DOUBLE SETPOINT” or “RESET SETPOINT” or “AMBIENT
COMPENSATION” is enabled)
5.6 Input/Output Menu ( I/O Menu )
This section shows the following parameters:
Software type, release
Digital Input and Output status (C, O)
Analogue Output value (Vdc)
Inlet and outlet water temperature, ambient temperature
Compressor discharge temperature and load
Condensation and oil pressure
Modem Status
Controller Bios and Boot version and date
SoftLoad Status
EXV Firmware version
5.7 Manufacturer menu
This section allows setting all manufacturer data. A password is required for the operation. The parameters may only be
modified by qualified persons.
Warning !
Incorrect setpoint or value can cause erratic chiller operation and damage to the chiller. Please use caution whenever
setpoints or parameters are changed.
Unit Configuration
00 = Air-cooled Chiller
01 = Water/Water Heat Pump
02 = Water/Water Pursuit Chiller
03 = Water-cooled Chiller
Enable sensor (Master Board)
B1, B2, B4, B6, B7, B8
Enable sensor (Slave Board)
B4, B6, B7, B8
Discharge sensor type (B4)
PT1000
Phase monitor type
UNIT
PID parameter
Integral time
Derivative time
Sampling time
200s
060s
030s
Compressor configuration
N. OF COMPRESSOR
Max number of pulses to load compressor
Max number of pulses to unload compressor
60
60
Min. time interval before a compressor is allowed to re-start
600 s
Min. time interval before any other compressor is allowed to start
120 s
Min running time for compressors
120 s
Min stop time for compressors
180 s
Interstage Timer
Double load/unload pulse for compressor load under
210 s
35%
PULSE TIME = 0.3 s
Compressor unloading pulse time
MIN. PULSE PERIOD = 1 s