Daikin EWWDC16CJYNN [18/28] Maintenance menu

Daikin EWWD480CJYNN [18/28] Maintenance menu
18
MAX. PULSE PERIOD = 10 s
PULSE TIME = 0.3 s
MIN. PULSE PERIOD = 20 s
Compressor loading pulse time
MAX. PULSE PERIOD = 90 s
ENABLE: YES
MAX. TIME = 60 s
Pumpdown configuration
MIN. PRESSURE = 0.5 bar
High pressure stage hold
17.5 bar
High pressure stage down
18.5 bar
Low pressure stage hold
1.7 bar
Low pressure stage down
1.2 bar
Antifreeze prevention
Setpoint
Diff.
3,5°C
1,0°C
Enable oil temperature control
Y
Enable evaporator flow alarm
YES (MASTER); NO (SLAVES)
Enable condenser flow alarm
YES (MASTER); NO (SLAVES)
START-UP DELAY = 20 s
Evaporator flow alarm delay (if enabled)
OPERATING DELAY = 5 s
SETPOINT = 120 °C
High discharge temperature setpoint
DIFFERENTIAL = 5 °C
SETPOINT = 20.5 bar
High pressure alarm setpoint
DIFFERENTIAL = 05.0 bar
SETPOINT = 01.0 bar
Low pressure alarm setpoint
DIFFERENTIAL = 00.5 bar
START-UP DELAY = 120 s
Low pressure alarm delay
OPERATING DELAY = 60 s
Pressure ratio alarm setpoint Min Load
Pressure ratio alarm setpoint Max Load
1,4
1,8
START-UP DELAY = 180 s
Pressure ratio alarm delay
OPERATING DELAY = 90 s
START-UP DELAY = 300 s
Low oil pressure alarm delay
OPERATING DELAY = 90 s
High oil differential pressure delay
20 sec
Max differential oil pressure
2.5 bar
SETPOINT = 02.0 °C
Freeze protection
DIFFERENTIAL = 01.0 °C
SETPOINT = 85,0 °C
Liquid injection
DIFFERENTIAL = 10,0 °C
SETPOINT = 3,0 °C
Evaporator heater
DIFFERENTIAL = 1,0 °C
PROTOCOL = CAREL
COMMUNICATION SPEED = 19200
Supervisor configuration
IDENTIFICATION NUMBER = 001
Default parameter?
NO
Modem connection password
0152
Password for driver configuration
Reserved area
5.8 Maintenance menu
In this section, it is possible to set the maintenance parameters by accessing the following forms:
Running time of evaporator pump/condenser pump
Running time and number of compressor starts
PID control status (only master)
Correction of pressure and temperature sensors
Correction of compressor running hours
Correction of compressor starts
Correction of compressor load sensor
By entering the maintenance password, it is possible to access the forms for maintenance parameters input.