Daikin EWYQ250DAYN [20/524] Technical specifications for options ewaq080 100dayn

Daikin EWAQ260DAYN [20/524] Technical specifications for options ewaq080 100dayn
General Outline ESIE06-05
1–8 Part 1 – System Outline
3
11
4
5
1.3 Technical Specifications for options: EWAQ080-100DAYN
Technical
specifications
The table below contains the technical specifications for the options of the EWAQ080-100 DAYN.
Technical specifications options
OPSP
Units EWAQ080DAYN* EWAQ100DAYN*
Weight Additional machine weight kg
250
250
Additional operation weight kg 283 283
Additional gross weight kg 250 250
Pump Type Single-stage-in-line-pumps Single-stage-in-line-pumps
Quantity 1 1
Model TP50-240/2 TP50-240/2
Nominal Static Height Unit kPa 142 133
Hydraulic components Additional unit water volume l 33 33
Expansion vessel l 35
Pre-charge pressure exp. vessel bar 1,5
Safety valve bar 3
OPSB + OPBT
Units EWAQ080DAYN* EWAQ100DAYN*
Weight
Additional machine weight kg 300 300
Additional operation weight kg 523 523
Additional gross weight kg 300 300
Pump
Type Single-stage-in-line-pumps Single-stage-in-line-pumps
Quantity 1 1
Model
TP50-240/2 TP50-240/2
Nominal Static Height Unit kPa 142 133
Hydraulic components
Buffer tank l 190 190
Additional unit water volume l 223 223
Expansion vessel l 35
Pre-charge pressure exp. vessel bar 1,5
Safety valve bar 3
OPHP
Units EWAQ080DAYN* EWAQ100DAYN*
Pump Type
Single-stage-in-line-pumps Single-stage-in-line-pumps
Quantity 1 1
Model TP50-240/2 TP50-240/2
Nominal Static Height Unit kPa 337 322