Daikin EWADC17C-XS [43/96] Electrical specifications

Daikin EWADC17C-XS [43/96] Electrical specifications
43
ELECTRICAL SPECIFICATIONS
EWAD C
-
PR
880
960
C10
C11
C13
C15
C14
810
MODEL
POWER SUPPLY
Phases
Nr
3
3
3
3
3
3
3
3
Frequency
Hz
50
50
50
50
50
50
50
50
Voltage
V
400
400
400
400
400
400
400
400
Voltage tolerance Minimum
%
-
10%
-
10%
-
10%
-
10%
-
10%
-
10%
-
10%
-
10%
Voltage tolerance Maximum
%
+10%
+10%
+10%
+10%
+10%
+10%
+10%
+10%
UNIT
Maximum starting current
A
618
653
653
917
964
1020
1020
1063
Nominal running current cooling
A
375
416
461
506
555
614
671
717
Mximum running current
A
509
552
596
660
719
788
858
911
Maximum current for wires sizing
A
555
603
651
721
785
861
937
996
FANS
Nominal running current cooling
A 47 47 47 52 52 57
62
62
COMPRESSORS
Phases
Nr
3
3
3
3
3
3
3
3
Voltage
V
400
400
400
400
400
400
400
400
Voltage tolerance Minimum
%
-
10%
-
10%
-
10%
-
10%
-
10%
-
10%
-
10%
-
10%
Voltage tolerance Maximum
%
+10%
+10%
+10%
+10%
+10%
+10%
+10%
+10%
Maximum running current
A
231
231
231
274
274
274
274
333
333
333
333
398
398
398
398
451
Starting method
---
Y
-
Y
-
Y
-
Y
-
Y
-
Y
-
Y
-
Y
-
EWAD C-PR
C16
MODEL
POWER SUPPLY
Phases
Nr
3
Frequency
Hz 50
Voltage V 400
Voltage tolerance Minimum
%
-
10%
Voltage tolerance Maximum % +10%
UNIT
Maximum starting current
A
1076
Nominal running current cooling
A
764
Mximum running current
A
964
Maximum current for
wires sizing
A
1054
FANS
Nominal running current cooling
A
62
COMPRESSORS
Phases
Nr
3
Voltage
V
400
Voltage tolerance Minimum
%
-
10%
Voltage tolerance Maximum
%
+10%
Maximum running current
A
451
451
Starting method
---
Y
-
Fluid: Water
Allowed voltage
tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
Maximum starting current: starting current of biggest compressor + current of the compressor at 75% maximum load + fans current for the circuit at 75%.
Nominal current in cooling mode is referred to the following conditions: evaporator 12/7°C; ambient 35°C; compressors + fans current.
Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current
Maximum unit current for wires sizing is based on minimum allowed voltage
Maximum current for wires sizing: (compressors full load ampere + fans current) x 1,1.