Daikin EWADC18C-XS [4/96] Features and benefits

Daikin EWAD880C-SR [4/96] Features and benefits
4
FEATURES AND BENEFITS
Versions
This unit is available in three different versions:
S: Standard Efficiency
X: High Efficiency
P: Premium Efficieny
The EER (Energy Efficiency Ratio) is the ratio of the Cooling Capacity to the Power Input of the
unit. The Power Input includes: the
power input for operation of the compressor, the power input of all control and safety devices, the power input for fans.
The ESEER (European Seasonal Energy Efficiency Ratio) is a weighed formula enabling to take into
EER with the load rate and the variation of air inlet condenser temperature.
ESEER = A x EER100% + B x EER75% + C x EER50% + D x EER25%
A
B C D
Coefficient 0.03 (3%) 0.33 (33%) 0.41 (41%) 0.23 (23%)
Air inlet condenser temperature 35°C 30°C 25°C 20°C
Sound configurations
Standard, low and reduced sound configurations available as follows:
-S: Standard Sound
Condenser fan rotating at 900 rpm, rubber antivibration under compressor
-L: Low Sound
Condenser fan rotating at 900 rpm, rubber antivibration under compressor, compressor sound enclosure.
-R: Reduced Sound
Condenser fan rotating at 700 rpm, rubber antivibration under compressor, compressor sound enclosure.