Daikin EWADC21C-XS [8/96] Options

Daikin EWADC11C-SR [8/96] Options
8
OPTIONS
Standard Options (supplied on basic unit)
Wye
-
Delta compressor starter (Y
-
-
For low inrush current and reduced starting torque
Double setpoint - Dual leaving water temperature setpoints.
Phase monitor
-
The phase monitor controls that phases sequence is correct and controls phase loss.
Evaporator victaulic kit
-
Hydraulic joint with gasket for an easy and quick water connection.
20mm evaporator insulation - The external shell is covered with a 20mm closed cell insulation material.
Evaporator electric heater
-
Electric heater (controlled by a thermostat) to protect the evaporator from freezing down to
-
28°C
ambient temperature, providing the power supply is on.
Electronic expansion valve
Discharge line shut-off valve - Installed on the discharge port of the compressor to facilitate maintenance operation.
Ambient outside temperature sensor and setpoint reset
Hour run meter
General fault contactor
Setpoint reset, Demand limit and Alarm from external device
-
(Set
-
point reset): The leaving water temperature set
-
point can be
overwritten with the following options: 4-20mA from external source (by user); outside ambient temperat
ure; evaporator water
temperature ∆t. - (Demand limit): User can limit the load of the unit by 4-20mA signal or by network system. -
(Alarm from external
device): Microprocessor is able to receive an alarm signal from an external device (eg. pump, etc…).
User can decide if this alarm signal
will stop or not the unit.
Fans circuit breakers
-
Safety device against motor overloading and short circuit
Main switch interlock door
Emergency stop
Options (on request)
MECHANICAL
Total heat recovery
-
Produced
with plate to plate or Shell&Tube heat exchangers to produce hot water.
Partial heat recovery
-
Produced with plate to plate heat exchangers to produce hot water.
Brine version
-
Allows the unit to operate down to
-
8°C leaving liquid temperature
(antifreeze required).
Evaporator flange kit
Condenser coil guards
Evaporator area guards
Cu
-
Cu condenser coil
-
To give better protection against corrosion by aggressive environments.
Cu
-
Cu
-
Sn condenser coil
-
To give better protection against
corrosion in aggressive environments and by salty air.
Alucoat fins coil
-
Fins are protected by a special acrylic paint with a high resistance to corrosion.
Suction line shut
-
off valve
-
Installed on the suction port of the compressor to facilitate
maintenance operation.
High pressure side manometers
Low pressure side manometers
One centrifugal pump (low lift)
-
Hydronic kit consists of: single direct driven centrifugal pump, water filling system with pressure
gauge, safety valve, drain valve. The
motor pump is protected by a circuit breaker installed in control panel. The kit is assembled and
wired to the control panel. The pipe and pump are protected from freezing with an additional electrical heater.
One centrifugal pump (high lift)
Hydronic kit
consists of: single direct driven centrifugal pump, water filling system with pressure
gauge, safety valve, drain valve. The motor pump is protected by a circuit breaker installed in control panel. The kit is ass
embled and
wired to the control panel. The pipe and pump are protected from freezing with an additional electrical heater.
Two centrifugal pump (low lift)
-
Hydronic kit consists of: twin direct driven centrifugal pumps, water filling system with pressure
gauge, safety valve, drain valve. The motor
pump is protected by a circuit breaker installed in control panel. The kit is assembled and
wired to the control panel. The pipe and pumps are protected from freezing with an additional electrical heater.
Two centrifugal pump (high lift)
Hydronic kit consi
sts of: twin direct driven centrifugal pumps, water filling system with pressure
gauge, safety valve, drain valve. The motor pump is protected by a circuit breaker installed in control panel. The kit is ass
embled and
wired to the control panel. The pipe and pumps are protected from freezing with an additional electrical heater.
Double pressure relief valve with diverter
Evaporator right water connections

Содержание