3 Specifications
Control panel
9 Field power connection, control interlock terminals, and unit control system should be centrally located in an electric panel (IP 54). Power and
starting controls should be separate from safety and operating controls in different compartments of the same panel.
9 Starting will be star/delta type as standard feature.
9 Power and starting controls should include fuses and contactors for each compressor winding and fan motors. Operating and safety controls should
include energy saving control; emergency stop switch; overload protection for compressor motor; high and low pressure cut-out switch (for each
refrigerant circuit); anti-freeze thermostat; cut-out switch for each compressor.
9 All of the information regarding the unit will be reported on a display and with the internal built-in calender and clock that will switch the unit ON/OFF
during day time all year long.
9 The following features and functions shall be included:
• resetting chilled water temperature
by controlling the return water temperature or by a remote 4-20 mA DC signal or by controlling the external
ambient temperature;
• soft load function
to prevent the system from operating at full load during the chilled fluid pulldown period;
• password protection
of critical parameters of control;
• start-to-start and stop-to-star timers
to provide minimum compressor off-time with maximum motor protection;
• communication capability
with a PC or remote monitoring;
• discharge pressure control
through intelligent cycling of condenser fans;
• lead-lag selection
by manual or automatically by circuit run hours;
• double set point
for brine unit version;
• scheduling
via internal time clock to allow programming of a yearly start-stop schedule accommodating weekends and holidays.
Display Capabilities
The controller as a minimum shall be capable of monitoring and displaying the following data:
Analogue Inputs (AI)
Digital Inputs (DI)
1 Entering Evaporator fluid Temp. 1 Control switch one per comp.
2 Leaving Evaporator fluid Temp. 2 Evaporator Fluid flow switch
3 Outside Air Temp 3 Phase monitor
4 Not Used 4 Double Setpoint (Ice Mode)
5 Discharge Press., one per comp. 5 High Press. Switch, one per compressor
6 Discharge Press., one per comp. 6 High Press. Switch, one per compressor
7 Setpoint Override (Setpoint Reset) 7 Low Press. Switch, one per compressor
8 Demand Limit or Current Limit (Site Selectable) 8 Oil Press. Switch, one per compressor
9 % Capacity Signal, one per comp. 9 Transition Fault, one per compressor
10 % Capacity Signal, one per comp. 10 Discharge Temp. Switch, one per comp.
11 External Alarm
Standard Customer Interfaces
The controller as a minimum shall be capable of providing the following interlocks: -
Chiller Enable Signal: Digital Input,
customer contact must be capable of handling 110Volts, 50HZ, 1Amp.
Chiller Common Fault: Volt free, normally open, digital contact,
Must be capable of switching 250V, 50HZ, 1Amp.
Pump Enable Signal: Volt free, normally open, digital contact,
Must be capable of switching 250V, 50HZ, 1Amp.
Setpoint Override: 4 – 20 mA DC analoque input signal.
Demand Limit: 4 – 20 mA DC analoque input signal.
Or
Current Limit: 4 – 20 mA DC analoque input signal.
Optional Customer Interfaces
Compressor Running Signals: Volt free, normally open, digital contact,
Capable of switching 250V, 50HZ, 1Amp.
Optional High Level Communications Interface
The controller as a minimum shall be capable of providing the data shown in the above list and document, using the following options:
Option A
RS485 Serial card Option B RS232 Serial card
Option C
LonWorks interface to FTT10A Transceiver. Option D Bacnet Compatible
Option E
Use of Compass Points (manufactured by North Communications) to allow communications with Such as Honeywell, Satchwell, Johnson
Controls, Trend etc.
Содержание
- Air cooled 2
- B 8400 ostend belgium 2
- Btw be 0412 120 336 2
- Eeden07 424 2
- Eeden07 424 04 2007 printed in belgium by goekint graphics copyright daikin 2
- Ewap ajynn 2
- Naamloze vennootschap 2
- Rpr oostende 2
- Www daikin eu 2
- Zandvoordestraat 300 2
- Chillers r 134a ewap ajynn 4
- Cooling only 4
- Heat pump 4
- Heating only 4
- Hydronic systems chillers 4 4
- Capacity correction factor 5
- Capacity table 5
- Cooling capacity tables 5
- Dimensional drawing 5
- Dimensional drawing centre of gravit 5
- Electrical specifications 5
- Feature 5
- Heat recovery pressure drop 5
- Heat recovery ratings 5
- Hydraulic performanc 5
- Installatio 5
- Installation method 5
- Nomenclatur 5
- Operation rang 5
- Option 5
- Pump characteristics 5
- Sound dat 5
- Sound level data 5
- Specification 5
- Table of contents ewap ajynn 5
- Technical specifications 5
- Water pressure drop curve evaporator 5
- Chillers r 407c ewap ajynn 6
- Features 6
- Hydronic systems chillers 6 6
- Chillers r 407c ewap ajynn 7
- Hydronic systems chillers 7 7
- Nomenclature 7
- Chillers r 407c ewap ajynn 8
- Hydronic systems chillers 8 8
- Specifications 8
- Chillers r 407c ewap ajynn 9
- Hydronic systems chillers 9 9
- Specifications 9
- Chillers r 407c ewap ajynn 10
- Hydronic systems chillers 10 10
- Specifications 10
- Chillers r 407c ewap ajynn 11
- Hydronic systems chillers 11 11
- Specifications 11
- 1 technical specifications 12
- Specifications 12
- 1 technical specifications 13
- Specifications 13
- 1 technical specifications 14
- Specifications 14
- 1 technical specifications 15
- Specifications 15
- 1 technical specifications 16
- Specifications 16
- 1 technical specifications 17
- Specifications 17
- 2 electrical specifications 18
- Specifications 18
- 2 electrical specifications 19
- Specifications 19
- Chillers r 407c ewap ajynn 20
- Hydronic systems chillers 20 20
- Options 20
- 1 cooling capacity tables 21
- Capacity tables 21
- 1 cooling capacity tables 22
- Capacity tables 22
- 1 cooling capacity tables 23
- Capacity tables 23
- 1 cooling capacity tables 24
- Capacity tables 24
- 1 cooling capacity tables 25
- Capacity tables 25
- 1 cooling capacity tables 26
- Capacity tables 26
- 1 cooling capacity tables 27
- Capacity tables 27
- 1 cooling capacity tables 28
- Capacity tables 28
- 2 capacity correction factor 29
- Capacity tables 29
- 3 heat recovery ratings 30
- Capacity tables 30
- 3 heat recovery ratings 31
- Capacity tables 31
- 3 heat recovery ratings 32
- Capacity tables 32
- 3 heat recovery ratings 33
- Capacity tables 33
- 1 dimensional drawing 34
- Dimensional drawing centre of gravity 34
- 1 sound level data 35
- Sound data 35
- 1 installation method 36
- Installation 36
- Chillers r 407c ewap ajynn 37
- Hydronic systems chillers 37 37
- Operation range 37
- 1 water pressure drop curve evaporator 38
- Hydraulic performance 38
- 2 pump characteristics 39
- Hydraulic performance 39
- 3 heat recovery pressure drop 40
- Hydraulic performance 40
- 3 heat recovery pressure drop 41
- Hydraulic performance 41
Похожие устройства
- Daikin EWAPC12AJYNN Схемы
- Daikin EWAPC12AJYNN Инструкция по монтажу
- Daikin EWAPC13AJYNN Схемы
- Daikin EWAPC13AJYNN Технические данные
- Daikin EWAPC13AJYNN Инструкция по монтажу
- Daikin EWAPC14AJYNN Технические данные
- Daikin EWAPC14AJYNN Схемы
- Daikin EWAPC14AJYNN Инструкция по монтажу
- Daikin EWAPC15AJYNN Схемы
- Daikin EWAPC15AJYNN Технические данные
- Daikin EWAPC15AJYNN Инструкция по монтажу
- Daikin EWAPC16AJYNN Схемы
- Daikin EWAPC16AJYNN Технические данные
- Daikin EWAPC16AJYNN Инструкция по монтажу
- Daikin EWAPC17AJYNN Технические данные
- Daikin EWAPC17AJYNN Схемы
- Daikin EWAPC17AJYNN Инструкция по монтажу
- Daikin EWAPC18AJYNN Технические данные
- Daikin EWAPC18AJYNN Схемы
- Daikin EWAPC18AJYNN Инструкция по монтажу