2.10 Lead-lag Control
Introduction This function only applies on units with double circuit.
The lead-lag mode determines which circuit starts up first in case of a capacity demand. It prevents
the unit from always starting up the same circuit.
Possible modes:
P Automatic: The controller decides whether circuit 1 or circuit 2 starts up first.
P Manual C1 > C2: Circuit 1 starts up before circuit 2. If circuit 1 is deactivated due to a failure, circuit
2 will start up instead.
P Manual C1 < C2: Circuit 2 starts up before circuit 1. If circuit 2 is deactivated due to a failure, circuit
1 will start up instead.
Remark: the different modes can be selected in the user settings menu.
Lead-lag hours in
automatic mode
When the lead-lag control is done automatically, the software calculates the differences in operation
time between the circuits. When this time is higher than the preset lead-lag hour value, the start
sequence of both circuits is swapped.
The limit values of the lead-lag hours are the following:
P lower limit: 100 hours
P upper limit: 1000 hours
P default value: 1000 hours
Remark: This value is important for maintenance purposes. It should be set high enough so that the
two compressors (if double circuit) do not require maintenance at the same time and that at least one
compressor can remain constantly active.
Equal start up
compressors
P Yes: both circuits will go up in capacity alternating.
P No: the leading circuit will go to full capacity before the lagging circuit can start up.