Daikin EWAD240MBYNN [424/452] Test run and operation data for ewap110 540mbynn

Daikin EWAP400MBYN [424/452] Test run and operation data for ewap110 540mbynn
Test Run and Operation Data ESIE05-07
4–18 Part 4 – Commissioning and Test Run
3
1
4
5
2.2 Test Run and Operation Data for EWAP110~540MBYNN
Pressures The table below contains the measurable pressures.
Temperatures The table below contains the measurable temperatures.
Voltages The table below contains the measurable voltages.
Currents The table below contains the currents and used fuses.
Measurement Value
Suction pressure
depending on working conditions
Discharge pressure
Maximum water pressure 10 bar
Measurement Value
Leaving water temperature
P Standard: 4 – 16°C
P With glycol: -10 – 16°C
Outdoor temperature -15 – 43°C
Temperature difference at the air side 10 – 15°C
Temperature difference at the water side 3 – 8°C
Discharge temperature 80 – 120°C
Approach temperature
(evap leaving water temp - sat. temp)
5 – 8°C (for MOW of 4°C)
for glycol units this can be > 8°C
Measurement Value
Power supply voltage Within ± 10% of the rated voltage
Phase imbalance Within ± 2% of the rated voltage
Control circuit voltage 230 V AC for main electromagnetic switches
24 V DC for the controllers
Unit Nominal current Maximum current Fuses
EWAP110MBYNN 70 A 95 A 3 x 125 gL A
EWAP140MBYNN 84 A 120 A 3 x 160 gL A
EWAP160MBYNN 104 A 135 A
EWAP200MBYNN 128 A 168 A 3 x 200 gL A
EWAP280MBYNN 180 A 232 A 3 x 250 gL A
EWAP340MBYNN 226 A 288 A 3 x 355 gL A
EWAP400MBYNN 258 A 342 A std: 6 x 250 gL A
op52: 3 x 400 gL A
ESIE05-07.book Page 18 Wednesday, October 11, 2006 10:42 AM

Содержание

Скачать