Daikin EWAD700BJYNN [181/346] Analog inputs

Daikin EWAD700BJYNN [181/346] Analog inputs
ESIE07-04 The Digital Controller
Part 2 – Functional Description 2–41
3
2
4
5
1
Analog inputs These screens show you the values of the analog inputs.
Remark : The oil pressure is measured by a pressure transducer connected to the oil supply chamber
of the compressor.
Remark : The oil temperature (delivery temperature) is measured in the oil separator with a PT1000
sensor.
Remark : The condensing pressure is measured by a pressure transducer connected to the oil
separator (B8).
P B1 : Oil pressure of compressor circuit 1
P B2 : Oil pressure of compressor circuit 2
P B3 : Read-out of the external signal used for setpoint reset (4-20 mA)
P B4 Del. Tem. 1 : Oil temperature (delivery temperature) of circuit 1
P B5 Del. Tem. 2 : Oil temperature (delivery temperature) of circuit 2
P B6 : Condensing pressure of circuit 1
P B7 : Condensing pressure of circuit 2
P B8 : Read-out of external signal used for demand limit (4-20 mA) or current limit if unit is SPN
unit.
P B9 : Inlet water temperature, measured in the inlet of the evaporator 1
P B10 : Outlet water temperature, measured in the outlet or common outlet (of evap 1 and 2) if
unit has 2 evaporators
Analog Inputs :
B1 : Oil pr. 1 00.0 bar
B2 : Oil pr.2 00.0 bar
Analog Inputs :
B3 : 00.0 mA
B4 : Del. Tem. 1 00.0 ˚C
B5 : Del. Tem. 2 00.0 ˚C
Analog Inputs :
B6 : Cond Pr. 1 00.0 bar
B7 : Cond Pr. 2 00.0 bar
B8 : 00.0 mA
Analog Inputs :
B9 : In Wtr 00.0 ˚C
B9 : Out Wtr 00.0 ˚C