Daikin EWAD600BJYNN/Q [178/346] Rs485 only

Daikin EWADC14BJYNN [178/346] Rs485 only
The Digital Controller ESIE07-04
2–38 Part 2 – Functional Description
3
1
2
4
5
Communication
supervisor
This screen is only visible when supervisor communication is selected.
Language This screen allows you to select the language of the controller.
Change user
password
This screen allows you to change the user password.
P Protocol :
CAREL : For BACnet communication (with gateway)
LONWORKS : Direct communication to BMS (Xif pre-loaded)
MODBUS : Direct communication to BMS
MODEM :
P Com speed :
19200 : RS485 only
9600 : RS485 only
4800 : RS485 / RS422
2400 : RS485 / RS422
1200 : RS485 / RS422
P Identification No : Number (address) of the chiller in the BMS system
Protocol : CAREL
Supervisor Com Speed
19200 (RS485 only)
Identificat. No. : 001
P Possible settings :
• ENGLISH
• FRENCH
• GERMAN
• ITALIAN
• SPANISH
Choose Language
ENGLISH
Change User Password
0000