Daikin ZHC7LSGU [13/58] Disassembly and inspection

Daikin ZHA7MSG [13/58] Disassembly and inspection
Overhaul Instructions Si50-402
12 Semi-Hermetic Single Screw Compressor Version IV
4.1 Disassembly and Inspection
1. Draining Oil
Drain oil by referring to Section 3.2.2 "Changing refrigerating oil."
2. Remove The Side Caps (One on Each Side) and The Discharge End Cover. (in case of
ZH9F, oil collector)
!
Receive remaining oil with a drain pan.
!
Be sure to mount guide bolts when removing the discharge end cover.
Furthermore, since continuous capacity control units have a pilot valve (as shown in Fig. 4-
2-2) inside, remove the discharge end cover with care paid not to bend this valve.
!
Be careful not to damage the oil filter with the discharge end cover.
!
Locate the first demister between the discharge end cover and cylinder cover, and remove it.
(Except ZH9F)
Fig. 4-1 Removing side cap Fig. 4-2 Removing discharge end cover
Fig. 4-2-2 Pilot valve Fig. 4-3
Removing first demiste
r
Pilot valve
(Z0128)