Daikin EWYP200CAYN [5/43] Specifications

Daikin EWYP095CAYN [5/43] Specifications
Chillers
R-407C
EWYP-CAYN
1
2
Hydronic Systems
5
2 Specifications
Hydraulic
components
Buffer tank volume l 570 570 570 570 570
Buffer tank additional height mm 400 400 400 400 400
Buffer tank additional gross
weight
kg 644 644 644 644 644
Hydraulic module weight kg 110 114 114 189 189
Antifreeze heater W 150 150 150 150 150
Unit water volume l 19.8 25.6 29 35.7 35.7
Expansion
vessel
Volume l 35 35 35 35 35
Max.
water
volume in
the
system
l 1400 1400 1400 1400 1400
Pre-
pressure
bar 1.5 1.5 1.5 1.5 1.5
Water filter inch 2 1/2 3 3 3 3
Safety valve bar 4 4 4 4 4
Fan Type Propeller
Drive Direct drive
Diameter mm 710 710 800 800 800
Nominal air flow m³/min 878 923 1438 1383 1321
Optional high
ESP
Max. Pa 80 80 60 60 60
Nom. Pa 80 80 60 60 60
Model Quantity 6 6 6 6 6
Speed rpm 700 700 680 680 680
Motor
Output
W 570 570 1400 1400 1400
Discharge direction Vertical
Quantity 6 6 6 6 6
Speed rpm 915 915 900 900 900
Motor
Output
W 1150 1150 2600 2600 2600
Discharge direction Vertical
Compressor Type Hermetically sealed scroll compressor
Refrigerant oil type POE ester oil
Refrigerant oil charge l 13.2 14.2 17.0 19.8 11.8
l 13.2 14.2 17.0 19.8 11.8
Model Quantity 4 6 6 6 4
Model 15T+15T 10T+10T+15T 15T+15T+10T 15T+15T+15T 25T+25T
Speed rpm 2900 2900 2900 2900 2900
Crankcas
e Heater
W 160 160 160 160 150
Sound Level Sound Power dBA 89 89 95 95 95
Sound Pressure dBA 57 57 63 63 63
Refrigerant
circuit
Refrigerant type R-407C
Refrigerant charge kg 24 29 30 34 41
kg 24 29 30 34 41
No of circuits 2 2 2 2 2
Refrigerant control Thermostatic expansion valve
Piping
connections
Evaporator water inlet/outlet ISO R7 2" 1/2 ISO R7 3" ISO R7 3" ISO R7 3" ISO R7 3"
Hose tube 15x21
Notes Nominal cooling capacity at Eurovent conditions: Evaporator 12°C/7°C; ambient 35°C
Nominal cooling power input at Eurovent conditions: Evaporator 12°C/7°C; ambient 35°C
2-1 TECHNICAL SPECIFICATIONS EWYP150CAYN EWYP170CAYN EWYP200CAYN EWYP220CAYN EWYP250CAYN

Содержание

Скачать