3-2 ELECTRICAL SPECIFICATIONS
EUWA060BZ6Y EUWA070BZ6Y EUWA080BZ6Y EUWA090BZ6Y EUWA095BZ6Y
Power Supply Name Y1
Phase 33333
FrequencyHz5050505050
Voltage V 400 400 400 400 400
Voltage Tolerance Minimum % -10%
Maximum % +10%
Unit Starting Current A 282 300 334 354 450
Nominal Running Current
Cooling
A 136.00 153.00 188.00 208.00 225.00
Compressor Power factor 0.85 0.85 0.85 0.85 0.87
NOTES
1 Nominal cooling capacity at Eurovent conditions: Evaporator 12°C/7°C; ambient 35°C
2 The sound power level is an absolute value indicating the "power" which a sound source generates.
3 The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value, depending on the distance and acoustic
environment.
4 For more details concerning conditional connections, see http://www.daikineurope.com/extranet, select ''Daikin Documentation'' and select ''conditional
connection'',''the requested product type'' and ''English'' from the drop down lists, click the search button. Finally, click on the document title of your choice.