TECHNICAL SPECIFICATIONS
Condenser fans
The condenser fans used in conjunction with the
condenser coils, shall be propeller type with glass reinforced
resin blades for higher efficiencies and lower sound. Each fan shall be protected by a fan guard.
• The air discharge shall be vertical and each fan must be coupled to the electrical motor, su
pplied as standard to IP54 and capable to
work to ambient temperatures of - 20°C to + 65°C.
• The condenser fans shall have as a standard an internally protection from overtemperature.
Refrigerant circuit The unit shall have two refrigerant circuits.
• The circuit shall include as standard: electronic expansion device piloted by unit’s microprocessor control, liquid line shut-
off valve,
sight glass with moisture indicator, replaceable filter drier, charging valves, high pressure switch, high and low pre
ssure transducers
and insulated suction line.
Condensation control
The units will be provided with an automatic control for condensing pressure which ensures the working
at low external temperatures down to - …………… °C, to maintain condensing pressure.
• The unit automatically unloads when abnormal high condensing pressure is detected. This to prevent the shutdown of the refriger
ant
circuit (shutdown of the unit) due to a high-pressure fault.
Low sound unit configurations (on request)
The unit compressor shall be connected with unit’s metal base frame by
rubber antivibration supports to prevent the transmission of vibrations to all metal unit structure, in order to control the unit sound.
• The chiller shall be provided with an acoustical compressor enclosure. This enclosure shall be realized with a light, corrosi
on resisting
aluminum structure and metal panels. The compressor sound-proof enclosure shall be internally fitted with flexible, multi-
layer, high
density materials.
Hydronic kit options (on request) The hydronic module shall be integrated in the chiller chassis without increasing its
dimensions and includes the following elements: centrifugal pump with motor protected by a circuit breaker installed in control panel,
water filling system with pressure gauge, safety valve, drain valve.
• The hydronic module shall be assembled and wired to the control panel.
• The water piping shall be protected against corrosion and freezing and insulated to prevent condensation.
• A choice of two pump types shall be available:
- in-line single pump
- in-line twin pumps.
Electrical control panel
Power and control shall be located in the main panel that will be manufactured to ensure protection
against all weather conditions.
• The electrical panel shall be IP54 and (when opening the doors) internally protected against possible accidental contact wi
th live
parts.
• The main panel shall be fitted with a main switch interlocked door that shuts off power supply when opening.
• The power section will include compressors and funs protection devices, compressors and fans starters and control circuit p
ower
supply.
Controller The controller will be installed as standard and it will be used to modify unit set-points and check control parameters.
• A built-
in display will shows chiller operating status plus temperatures and pressures of water, refrigerant and air, programmable
values, set-points.
• A sophisticated software with predictive logic, will select the mos
t energy efficient combination of compressors, EEXV and condenser
fans to keep stable operating conditions to maximize chiller energy efficiency and reliability.
• The controller will be able to protect critical components based on external signals from it
s system (such as motor temperatures,
refrigerant gas and oil pressures, correct phase sequence, pressure switches and evaporator). The input coming from the high
pressure
switch cuts all digital output from the controller in less than 50ms, this will be an additional security for the equipment.
• Fast program cycle (200ms) for a precise monitoring of the system.
• Floating point calculations supported for increased accuracy in P/T conversions.
Pagina 65 di 67
Содержание
- Air cooled scroll chillers 1
- Databook 1
- Ewaq f 1
- Performance according to en14511 1
- Certifications 2
- Code requirements safety and observant of laws directives 2
- Features and benefits 2
- Low operating cost and extended operating life 2
- Low operating sound levels 2
- Outstanding reliability 2
- Pagina 2 di 67 2
- Sound configurations 2
- Superior control logic 2
- Versions 2
- Cabinet and structure 3
- Compressor 3
- Condenser 3
- Condenser fans ø 800 3
- Electrical control panel 3
- Electronic expansion valve 3
- Evaporator plate heat exchanger 3
- General characteristics 3
- Pagina 3 di 67 3
- Refrigerant 3
- Refrigerant circuit 3
- General characteristics 4
- Pagina 4 di 67 4
- Supervising systems on request 4
- Options 5
- Options on request 5
- Pagina 5 di 67 5
- Standard options supplied on basic unit 5
- Options 6
- Pagina 6 di 67 6
- Capacity class in kw cooling 7
- Efficiency level 7
- Inverter 7
- Machine type 7
- Model series 7
- Nomenclature 7
- Pagina 7 di 67 7
- Refrigerant 7
- Sound level 7
- Ewaq f ss 8
- Pagina 8 di 67 8
- Technical specifications 8
- Ewaq f ss 9
- Pagina 9 di 67 9
- Technical specifications 9
- Ewaq f sl 10
- Pagina 10 di 67 10
- Technical specifications 10
- Ewaq f sl 11
- Pagina 11 di 67 11
- Technical specifications 11
- Ewaq f sr 12
- Pagina 12 di 67 12
- Technical specifications 12
- Ewaq f sr 13
- Pagina 13 di 67 13
- Technical specifications 13
- Ewaq f xs 14
- Pagina 14 di 67 14
- Technical specifications 14
- Ewaq f xs 15
- Pagina 15 di 67 15
- Technical specifications 15
- Ewaq f xl 16
- Pagina 16 di 67 16
- Technical specifications 16
- Ewaq f xl 17
- Pagina 17 di 67 17
- Technical specifications 17
- Ewaq f xr 18
- Pagina 18 di 67 18
- Technical specifications 18
- Ewaq f xr 19
- Pagina 19 di 67 19
- Technical specifications 19
- Electrical specifications 20
- Ewaq f ss 20
- Pagina 20 di 67 20
- Electrical specifications 21
- Ewaq f sl 21
- Pagina 21 di 67 21
- Electrical specifications 22
- Ewaq f sr 22
- Pagina 22 di 67 22
- Electrical specifications 23
- Ewaq f xs 23
- Pagina 23 di 67 23
- Electrical specifications 24
- Ewaq f xl 24
- Pagina 24 di 67 24
- Electrical specifications 25
- Ewaq f xr 25
- Pagina 25 di 67 25
- Ewaq f sl 26
- Ewaq f sr 26
- Ewaq f ss 26
- Pagina 26 di 67 26
- Sound levels 26
- Ewaq f xl 27
- Ewaq f xr 27
- Ewaq f xs 27
- Pagina 27 di 67 27
- Sound levels 27
- Operating limits 28
- Pagina 28 di 67 28
- Table 1 water heat exchanger minimum and maximum water δt 28
- Table 2 water heat exchanger fouling factors 28
- Operating limits 29
- Pagina 29 di 67 29
- Table 3 air heat exchanger altitude correction factors 29
- Table 4 minimum glycol percentage for low air ambient temperature 29
- Table 5 available fan static pressure correction factors 29
- Operating limits 30
- Pagina 30 di 67 30
- Water charge flow and quality 30
- Water content in cooling circuits 30
- Cooling performance 32
- Ewaq f ss 32
- Pagina 32 di 67 32
- Cooling performance 33
- Ewaq f ss 33
- Pagina 33 di 67 33
- Cooling performance 34
- Ewaq f ss 34
- Pagina 34 di 67 34
- Cooling performance 35
- Ewaq f sl 35
- Pagina 35 di 67 35
- Cooling performance 36
- Ewaq f sl 36
- Pagina 36 di 67 36
- Cooling performance 37
- Ewaq f sl 37
- Pagina 37 di 67 37
- Cooling performance 38
- Ewaq f sr 38
- Pagina 38 di 67 38
- Cooling performance 39
- Ewaq f sr 39
- Pagina 39 di 67 39
- Cooling performance 40
- Ewaq f sr 40
- Pagina 40 di 67 40
- Cooling performance 41
- Ewaq f xs 41
- Pagina 41 di 67 41
- Cooling performance 42
- Ewaq f xs 42
- Pagina 42 di 67 42
- Cooling performance 43
- Ewaq f xs 43
- Pagina 43 di 67 43
- Cooling performance 44
- Ewaq f xs 44
- Pagina 44 di 67 44
- Cooling performance 45
- Ewaq f xl 45
- Pagina 45 di 67 45
- Cooling performance 46
- Ewaq f xl 46
- Pagina 46 di 67 46
- Cooling performance 47
- Ewaq f xl 47
- Pagina 47 di 67 47
- Cooling performance 48
- Ewaq f xl 48
- Pagina 48 di 67 48
- Cooling performance 49
- Ewaq f xr 49
- Pagina 49 di 67 49
- Cooling performance 50
- Ewaq f xr 50
- Pagina 50 di 67 50
- Cooling performance 51
- Ewaq f xr 51
- Pagina 51 di 67 51
- Cooling performance 52
- Ewaq f xr 52
- Pagina 52 di 67 52
- Options technical data 53
- Pagina 53 di 67 53
- Single pump 2 poles 53
- Water pump kit 53
- Options technical data 54
- Pagina 54 di 67 54
- Twin pump 2 poles 54
- Water pump kit combination matrix 54
- Options technical data 55
- Options technical data 56
- Pagina 56 di 67 56
- Water pump kit technical information 56
- 2 3 4 5 6 7 8 57
- A m l i h g b c f e d 57
- Compressor evaporator condenser coil electrical panel fan evaporator water inlet evaporator water outlet slot for power and control panel connection 57
- Dimensional drawing 57
- Legend 57
- Pagina 57 di 67 57
- 2 3 4 5 6 7 8 58
- A m l i h g b c f e d 58
- Compressor evaporator condenser coil electrical panel fan evaporator water inlet evaporator water outlet slot for power and control panel connection 58
- Dimensional drawing 58
- Legend 58
- Pagina 58 di 67 58
- 2 3 4 5 6 7 8 59
- A m l i h g b c f e d 59
- Compressor evaporator condenser coil electrical panel fan evaporator water inlet evaporator water outlet slot for power and control panel connection 59
- Dimensional drawing 59
- Legend 59
- Pagina 59 di 67 59
- 2 3 4 5 6 7 8 60
- A m l i h g b c f e d 60
- Compressor evaporator condenser coil electrical panel fan evaporator water inlet evaporator water outlet slot for power and control panel connection 60
- Dimensional drawing 60
- Legend 60
- Pagina 60 di 67 60
- Handling 61
- Installation notes 61
- Location 61
- Pagina 61 di 67 61
- Space requirements 61
- Warning 61
- Installation notes 62
- Installation notes 63
- Pagina 63 di 67 63
- Condenser coil 64
- Dimensions 64
- Evaporator phe 64
- General 64
- Pagina 64 di 67 64
- Performance 64
- Refrigerant 64
- Sound level and vibrations 64
- Technical specifications 64
- Unit description 64
- Condensation control 65
- Condenser fans 65
- Controller 65
- Electrical control panel 65
- Hydronic kit options on request 65
- Low sound unit configurations on request 65
- Pagina 65 di 67 65
- Refrigerant circuit 65
- Technical specifications 65
- Controller main features 66
- High level communications interface on request 66
- Pagina 66 di 67 66
- Technical specifications 66
Похожие устройства
- Daikin EWAQ230F-SL Инструкция по монтажу
- Daikin EWAQ230F-SL Инструкция по эксплуатации
- Daikin EWAQ230F-SL Технические данные
- Daikin EWAQ250F-SL Инструкция по монтажу
- Daikin EWAQ250F-SL Инструкция по эксплуатации
- Daikin EWAQ250F-SL Технические данные
- Daikin EWAQ280F-SL Инструкция по монтажу
- Daikin EWAQ280F-SL Инструкция по эксплуатации
- Daikin EWAQ280F-SL Технические данные
- Daikin EWAQ320F-SL Инструкция по монтажу
- Daikin EWAQ320F-SL Инструкция по эксплуатации
- Daikin EWAQ320F-SL Технические данные
- Daikin EWAQ350F-SL Инструкция по монтажу
- Daikin EWAQ350F-SL Инструкция по эксплуатации
- Daikin EWAQ350F-SL Технические данные
- Daikin EWAQ360F-SL Инструкция по монтажу
- Daikin EWAQ360F-SL Инструкция по эксплуатации
- Daikin EWAQ360F-SL Технические данные
- Daikin EWAQ400F-SL Инструкция по монтажу
- Daikin EWAQ400F-SL Инструкция по эксплуатации