Daikin EWAQ310F-XL [10/250] D eimac00808 16eu 10

Daikin EWAQ310F-XL [10/250] D eimac00808 16eu 10
D-EIMAC00808-16EU - 10
Label Identification
Figure 2 - Operating limits
Note
The above graphic represents a guidelines about the operating limits of the range. Please refer to Chiller Selection Software
(CSS) for real operating limits working conditions for each size.
Legend
CIAT = Condenser Inlet Air Temperature (°C)
ELWT = Evaporator Leaving Water Temperature (°C)
A = Operation with Glycol (below 4°C Evap LWT)
B = Fan speed modulation or Speedtroll required (below 10°C Condens. Air Temp.)
C = Fan speed modulation or Speedtroll required (below 10°C and up to -10°C Condens. Air Temp.)*
*Only referred to units with 4-5-6 fans
D = In this area units can work at partial load
E = In this area the unit minimum capacity might be higher than value shown in Technical Specification table
F = Standard Efficiency (standard sound)
G = High Efficiency (standard sound)
1 Non flammable gas symbol
5 Cable tightening warning
2 Gas type
6 Hazardous Voltage warning
3 Unit nameplate data
7 Electrical hazard symbol
4 Manufacturer’s logo
8 Lifting instructions