Daikin EWWD900I-SS [19/51] Capacity tables

Daikin EWWD800I-SS [19/51] Capacity tables
3
1
4
Hydronic Systems • Single Unit
19
Single Unit • Water cooled chiller, standard efficiency • EWWD-I-SS
4 Capacity tables
4 - 2 Partial Heat Recovery Capacity tables
OPT_1-2-3-4-5-6-7-8_Rev.00_4
NOTES
Leaving Evaporator Water Te mperature 7°C, ǻT 5°C; ǻT Condenser Water Temperature 5°C
Partial Heat Recovery Ratings
EWWD~I-SS
Size
ELWT (°C)
Leaving Condenser Water Temperature (°C)
35 40 45 50 55
Hc (kW) Hc (kW) Hc (kW) Hc (kW) Hc (kW)
340
40 33 45 57 57 58
45 25 36 48 61 56
50 16 28 39 52 51
400
40 37 50 62 68 68
45 28 40 53 65 67
50 18 31 44 55 61
460
40 48 62 77 79 80
45 36 51 66 83 78
50 24 39 55 75 71
550
40 55 73 91 94 95
45 40 59 78 91 92
50 26 45 65 78 84
650
40 65 86 107 111 111
45 48 70 92 107 108
50 32 54 76 92 99
700
40 68 93 118 122 123
45 51 76 101 118 119
50 34 59 84 101 109
800
40 73 101 130 135 136
45 54 83 112 130 132
50 36 65 93 112 121
850
40 83 112 141 146 147
45 62 91 121 141 143
50 41 71 101 121 131
900
40 93 123 152 157 158
45 70 100 130 152 154
50 46 77 108 130 141
950
40 99 132 165 171 172
45 73 107 141 165 167
50 48 83 118 141 153
C10
40 103 138 174 180 182
45 76 113 149 174 177
50 50 87 124 149 162
C12
40 123 158 193 200 201
45 92 128 165 193 195
50 60 97 133 165 179
C13
40 127 164 201 208 210
45 94 133 172 201 204
50 62 101 139 172 187
C14
40 132 172 213 220 222
45 98 140 182 213 216
50 64 106 147 182 198
C15
40 138 182 227 235 236
45 102 148 194 227 230
50 67 108 148 194 210
C16
40 143 190 237 245 247
45 105 154 203 237 240
50 69 112 155 203 220
C17
40 149 198 247 255 257
45 109 160 211 247 250
50 71 117 162 211 229
C18
40 154 205 257 266 268
45 126 173 220 257 260
50 73 117 161 220 238

Содержание