Daikin EUWL12KZW [5/21] Specification text
2
Specification text
Unit construction
Compact, modular design chiller without condenser for indoor installation IP20 - manufactured according to the lSO 9001 quality standard.
The EUWL-KZW range has been designed for both air conditioning and process cooling applications. The use of state-of-the-art
technologies and high quality materials ensures efficiency, reliability and an extended service life.
Casing / Colour
Powder coated, galvanised steel plate. Fully factory assembled on a base frame. Colour ivory white (± RAL 9044) / Munsell code 5Y7.5/1
Number of cooling circuits
Module size 5-12 single circuit, 16-24 double circuit.
Each refrigerant circuit has its own independent design thereby guaranteeing a high level of system reliability.
The EUWL16-24KZW units have 2 plate heat exchangers (two refrigerant circuits / one water circuit) in order to minimise the hydraulic
installation overhead.
Compressor
One R-407C optimised fully hermetically sealed DAlKIN scroll type compressor per refrigerant circuit. As a design requirement, this
compressor characteristically offers extremely smooth performance, efficiency and operational reliability. Each compressor is mounted in the
unit with vibration isolation and fitted with a compressor motor overcurrent (Klixon).
Condenser
Local capacity !
Evaporator
R-407C optimised DX counter flow plate heat exchanger made of stainless steel, plates brazed gastight with copper, for water and glycol
mixtures. A special refrigerant distribution system has been incorporated into the plate duct for optimal capacity of the complete heat
transmission surface. As well as an additional increase in efficiency, this is also responsible for stable control behaviour in the heat
exchanger. The plate heat exchanger is heat-insulated to ensure it is diffusion-proof to prevent any heat loss. Electronic contactor and water
filter as standard. The water pressure may not exceed the maximum permissible operating pressure of 10 bar!
Piping
Consisting of Cu pipe with all the necessary cooling fittings such as:
service valves, filter-driers, inspection glass, solenoid valve, TEV with external pressure equalisation and accumulator. The refrigerant circuit is
subjected to factory pressure and leak testing, is cleaned, dried, evacuated and filled with an inert gas and filled with oil ready for operation.
Safety and control devices
Each refrigerant circuit has the following safety devices:
High- and low-pressure switch, hot gas temperature monitoring, compressor thermal cut-out, overload relay, frost protection.
Each refrigerant circuit is fitted with the following control devices:
Electronic temperature monitoring, phase-sequence relay, timing safety device and switch frequency limiter.
Remote condenser R-407C EUWL5-24KZW
1
2
3
Applied Systems Chillers
Скачать