Daikin EWAD220TZ-XLB1 [8/104] General characteristics

Daikin EWAD220TZ-XLB1 [8/104] General characteristics
Refrigerant circuit
Eachunithasoneortwoindependentrefrigerantcircuitsandeachoneincludes:

•CompressorInverterdrivenwithintegratedoilseparator

•Refrigerant

•Evaporator

•AirCooledCondenser

•Electronicexpansionvalve

•Dischargelineshutoffvalve

•Liquidlineshutoffvalve

•Sightglasswithmoistureindicator

•Filterdrier

•Economizercircuitwithelectronicexpansionvalve

•Chargingvalves

•Highpressureswitch

•Highpressuretransducers

•Lowpressuretransducers

•Oilpressuretransducer

•Suctiontemperaturesensor
Electrical control panel Power and control are located in the main panel that is manufactured to ensure
protectionagainstallweatherconditions.TheelectricalpanelisIP54and(whenopeningthedoors)internally
protected against possible accidental contact with live parts. The main panel is fitted with a main switch
interlockeddoorthatshutsoffpowersupplywhenopening.

Power Section Thepowersectionincludescompressorsandfansprotectiondevices,fansstartersandcontrol
circuitpowersupply.
MicroTech III controller MicroTechIIIcontrollerisinstalledasstandard;itcanbeusedtomodifyunitset-
pointsandcheckcontrolparameters.Abuilt-in displayshows chiller operatingstatusplus temperaturesand
pressures of water, refrigerant and air, programmable values, set-points. A sophisticated software with
predictive logic, selects the most energy efficient combination of compressors, EEXV and condenser fans to
keep stableoperating conditionstomaximizechillerenergy efficiencyandreliability.MicroTechIIIisable to
protectcriticalcomponentsbasedonexternalsignalsfromitssystem(suchasmotortemperatures,refrigerant
gasandoilpressures,correctphasesequence,pressureswitchesandevaporator).Theinputcomingfromthe
highpressureswitchcutsalldigitaloutputfromthecontrollerinlessthan50ms,thisisanadditionalsecurity
for the equipment. Fast program cycle (200ms) for a precise monitoring of the system. Floating point
calculationssupportedforincreasedaccuracyinPressure/Temperatureconversions.
Control section - main features
ControlSectionhasthefollowingfeature.
•Managementofthecompressorsteplesscapacityandfansmodulation.
•Chillerenabledtoworkinpartialfailurecondition.
•Fullroutineoperationatconditionof:
-highambienttemperaturevalue
-highthermalload
-highevaporatorenteringwatertemperature(start-up)
•Displayofevaporatorentering/leavingwatertemperature.
•DisplayofOutdoorAmbientTemperature.
 • Display of condensing-evaporating temperature and pressure, suction and discharge superheat for each
circuit.
•Leavingwaterevaporatortemperatureregulation.
•Compressorandevaporatorpumpshourscounter.
•DisplayofStatusSafetyDevices.
•Numberofstartsandcompressorworkinghours.
•Optimizedmanagementofcompressorload.
•Fanmanagementaccordingtocondensingpressure.
•Re-startincaseofpowerfailure(automatic/manual).
•SoftLoad(optimizedmanagementofthecompressorloadduringthestart-up).
•Startathighevaporatorwatertemperature.
8/104
GENERAL CHARACTERISTICS