Daikin EWAH530TZ-SSB2 [56/102] Ewah tz ssb

Daikin EWAH330TZ-SSB1 [56/102] Ewah tz ssb
55/100
SOUND LEVELS
EWAH~TZ-SSB
Sound pressure level at 1 m from the unit (rif. 2 x 10-5 Pa)
Power db
(A)
MODEL
63 Hz
250 Hz
500 Hz
2000 Hz
4000 Hz
8000 Hz
db(A)
170
78.9
74.9
77.9
67.9
60.9
52.9
78
97
200
79.4
75.4
78.4
68.4
61.4
53.4
79
98
240
81.5
77.5
80.5
70.5
63.5
55.5
81
100
290
81.8
78.8
81.8
71.8
63.8
56.8
82
101
330
81.8
78.8
81.8
71.8
63.8
56.8
82
101
390
80.1
77.1
80.1
70.1
62.1
55.1
80
101
420
80.5
77.5
80.5
70.5
62.5
55.5
81
101
490
82.3
79.3
82.3
72.3
64.3
57.3
82
103
530
84.7
81.7
84.7
74.7
66.7
59.7
85
106
600
83.5
80.5
83.5
73.5
65.5
58.5
83
104
690
83.2
80.2
83.2
73.2
65.2
58.2
83
104
750
82.8
79.8
82.8
72.8
64.8
57.8
83
104
820
67.2
76.0
83.7
75.3
67.2
59.8
84
105
920
68.4
77.2
84.9
76.5
68.4
61.0
85
106
980
68.8
77.6
85.3
76.9
68.8
61.4
85
107
C10
69.5
78.3
86.0
77.6
69.5
62.1
86
108
Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and
Eurovent 8/1 for Eurovent certified units. The certification refers only to the overall sound power level.
The sound data in the Octave band spectrum is for intended for reference only and not considering binding.
The sound pressure is calculated from the sound power level and are for information only and not considered binding.
The data are referred to the standard unit without options.

Содержание

Скачать