Daikin EWWD650EJYNN [20/23] Operating limits

Daikin EWWD340EJYNN [20/23] Operating limits
3
1
8
Applied Systems • Chillers
20
Chillers • R-134A • EWWD-EJYNN/A
8 Operation range
Operating limits
EWWD-EJ; EWWD-EJ/A R-134a
Max evaporator leaving water temperature °C
15
Min evaporator leaving water temperature (without glycol) °C
4
Min evaporator leaving water temperature (with glycol) °C
-8
Min evaporator water
T
°C
4
Max evaporator water
T
°C
8
Min
T between leaving water evaporator and leav. water condenser
°C
16
Max
T between leaving water evaporator and leav. water condenser
°C
48
Min condenser entering water temperature °C
15
Max condenser leaving water temperature °C
55
Min condenser water
T (1 pass, 2 passes -
T 4÷8 °C)
°C
4
Max condenser water
T (1 pass, 2 passes -
T 4÷8 °C)
°C
8
Min condenser water
T (2 passes -
T 8÷15 °C)
°C
8
Max condenser water
T (2 passes -
T 8÷15 °C)
°C
15
Скачать