Daikin EWWD700EJYNN [5/23] Specifications

Daikin EWWD340EJYNN [5/23] Specifications
Chillers • R-134A • EWWD-EJYNN/A
1
2
Applied Systems • Chillers
5
2 Specifications
Unit Starting Current A 303 464 464 464 303 464
Maximum starting current A 303 464 464 464 454 615
Starting current soft start A 585 726 846 963 736 897
Nominal Running Current
Cooling
A 117 144 165 193 234 260
Power factor at nominal
conditions
A 0.87 0.86 0.88 0.90 0.87 0.86
Maximum Running Current A 195 242 282 321 390 437
Max unit current for wires
sizing
A 214.5 266.2 310.2 353.1 429 480.7
Recommended fuses according to
IEC standard 269-2
3x355 A gG 3x400 A gG 3x400 A gG 3x500 A gG 3x500 A gG 3x500 A gG
Compressor Starting current A 303 464 464 464 303 303
Nominal running current
(RLA)
A 117 144 165 195 117 117
Maximum Running Current A 195 242 282 321 195 195
Power factor 0.87 0.86 0.88 0.89 0.87 0.87
Starting Method Open Wye - Delta
Recommended fuses Factory installed
Starting current A
-
303 464
Nominal running current
(RLA)
A 117 143
Maximum Running Current A 195 242
Power factor 0.87 0.86
Starting Method Open Wye - Delta Open Wye - Delta
Recommended fuses Factory installed Factory installed
Control Circuit Phase 1~
Frequency Hz 50 50 50 50 50 50
Voltage V 120 120 120 120 120 120
Recommended fuses Factory installed
Crankcase heater (E1/2HC) W 250 W - 400 V
Evaporator
Heater Tape
Supply Voltage V 120 120 120 120 120 120
Capacity W 150 150 150 150 150 150
Voltage
Tolerance
Minimum % -10%
Maximum % +10%
Recommended fuses Factory installed
Notes Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
Nominal current in cooling mode is referred to installation with 25kA short circuit current and is based on the following
conditions: evaporator 12/7°C, condenser 30/35°C
Maximum starting current: starting current of biggest compressor + current of the other compressor at 75 % of
maximum load
Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1
Recommended fuses (IEC 269-2: 1.6 times largest compressor fuse size)
2-2 ELECTRICAL SPECIFICATIONS
EWWD850EJYNN/A EWWD950EJYNN/A EWWDC10EJYNN/A EWWDC11EJYNN/A EWWDC12EJYNN/A
Power Supply Name YN
Phase 3~
Frequency Hz 50
Voltage V 400
Voltage
Tolerance
Minimum % -10%
Maximum % +10%
2-2 ELECTRICAL SPECIFICATIONS
EWWD360EJYNN/
A
EWWD440EJYNN/
A
EWWD500EJYNN/
A
EWWD600EJYNN/
A
EWWD750EJYNN/
A
EWWD800EJYNN/
A