Daikin EWWD440EJYNN/A [10/26] Specifications

Daikin EWWD340EJYNN [10/26] Specifications
3
1
2
Applied Systems • Chillers
10
Chillers • R-134A • EWWD-EJYNN
2 Specifications
Notes Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
Nominal current in cooling mode is referred to installation with 25kA short circuit current and is based on the following
conditions: evaporator 12/7°C, condenser 30/35°C
Maximum starting current: starting current of biggest compressor + current of the other compressor at 75 % of
maximum load
Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1
Recommended fuses (IEC 269-2: 1.6 times largest compressor fuse size)
2-2 ELECTRICAL SPECIFICATIONS
EWWDC14EJYNN EWWDC15EJYNN EWWDC16EJYNN EWWDC17EJYNN EWWDC18EJYNN
Скачать