D-EOMHP00706-14EN - 11/78
Direct intervention on the power supply can cause electrocution, burns or even death.
This action must be performed only by trained persons.
Flowswitch
The unit must be protected by a flow switch. The flow switch will stop the unit when the water flow
becomes lower than the minimum allowed flow. When the water flow is restored the flow protection
is reset automatically. Exception is when the flow switch opens with at least one compressor running,
in this case the alarm shall be cleared manually.
Freezing protection
Antifreeze protection prevents the water to freeze in the evaporator. It is automatically activated when
the water temperature (entering or leaving) at the evaporator drops below the antifreeze limit. In freeze
condition if the unit is in standby the evaporator pump will be activated to prevent freezing of the
evaporator. If the freeze condition will activate when the unit is running all units will shut down in alarm
while the pump will keep running. Alarm will automatically clear when the freeze condition will clear.
Low pressure protection
If the circuit operates with a suction pressure lower than an adjustable limit for a certain time the circuit
safety logic will shut down the circuit and generate an alarm. The alarm requires a manual action on the
Unit Controller to be reset. Reset will take effect only if the suction pressure is no longer lower that the
safety limit.
High Pressure Protection
If the discharge pressure becomes too high and exceeds a limit which is linked with the operational
envelop of the compressor the circuit safety logic will try to prevent the alarm or, if the corrective actions
have no effect, it will shut down the circuit before the Mechanical High Pressure switch will open. This
alarm required a manual action on the Unit Controller to be reset.
Mechanical High Pressure Switch
Each circuit is equipped with at least one high pressure switch which tries to prevent the relief safety
valve to open. When the discharge pressure becomes too high the Mechanical High Pressure switch will
open and immediately stop the compressor cutting the power supply to the auxiliary relay. The alarm can
be cleared as soon as the discharge pressure becomes normal again. The alarm must be reset on the
switch itself and on the Unit Controller. The triggering pressure value cannot be changed.