ELECTRICAL SPECIFICATIONS
EWAD~T-XRB
40/73
MODEL
EWADH18T-
XR B3
EWADC19T-
XR B3
EWADC20T-
XR B3
POWER SUPPLY
No.
3
3
3
Hz
50
50
50
V
400
400
400
Voltage tolerance Minimum %
-10%
-10%
-10%
Voltage tolerance Maximum %
10%
10%
10%
UNIT
A
1204
1253
1301
A
995
1067
1134
A
1239
1299
1360
A
1358
1425
1491
A
43.2
43.2
43.2
COMPRESSORS
No.
3
3
3
V
400
400
400
Voltage tolerance Minimum %
-10%
-10%
-10%
Voltage tolerance Maximum %
10%
10%
10%
A
398
459
459
Starting method
Y-Δ
Y-Δ
Y-Δ
Fluid: Water
Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load.
In case of inverter driven units, no inrush current at start up is experienced.
Nominal current in cooling mode is referred to the following conditions: evaporator 12/7°C; ambient 35°C; compressors + fans current.
Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current
Maximum unit current for wires sizing is based on minimum allowed voltage
Maximum current for wires sizing: (compressors full load ampere + fans current) x 1,1.
The data are referred to the standard unit without options.
For the electrical data of the hydronic kit refer to "Options technical data"
All data are subject to change without notice. Please refer to unit nameplate data.