Daikin EWAD820T-XSB2 [10/81] Mechanical options on request

Daikin EWAD540T-XSB2 [10/81] Mechanical options on request
OPTIONS
10/73
with Master / Slave control is possible to:
- balance the working hours of the compressors enhancing reliability and extending the life of the
system;
- balancing the load between the units to maximize the efficiency of the system;
In order to operate in Master / Slave mode an additional probe (PT1000 or NTC10K) must be installed
on the common line of the plant and connected to the master unit. The additional probe is not provided
by the factory. Master / Slave can manage units selected with pump on board (fix speed and inverter
driven pumps).
Note: check valves must be installed at the outlet of each chiller. Master / Slave can also manage the start
and stop of external pumps (not provided by factory). The power supply of external pumps is not
provided by the unit.
Mechanical options (on request)
Total Heat Recovery (opt. code 01) A plate to plate heat exchanger for each refrigerant circuit is
installed in series to the air condenser coil. There is no switch nor solenoid valve in the circuit, thus
compressor discharged refrigerant is always flowing through the heat recovery exchanger and warm
water production is always available while the chiller is providing cooling. The amount of heat recovered
is about the 80/85% (according to the operating conditions) of the total heat rejection of the chiller. The
chiller perform the control on the recovery circuit, based on the return water temperature to the unit. Heat
recovery capability is subject to cooling load demand (if no cooling demand is present then no heat
recovery is available) - Opt. incompatibility: 03
Partial Heat Recovery (opt. code 03) A plate to plate heat exchanger for each refrigerant circuit is
installed in series to the air condenser coil. There is no switch nor solenoid valve in the circuit, thus
compressor discharged refrigerant is always flowing through the heat recovery exchanger and warm
water production is always available while the chiller is providing cooling. The unit controller does not
manage the partial heat recover operation. The recover must be managed from the plant manager that
controls the operation of the pump on the recovery circuit. The amount of heat recovered is about the
15/20% (according to the operating conditions) of the total heat rejection of the chiller. Heat recovery
capability is subject to cooling load demand (if no cooling demand is present then no heat recovery is
available) - Opt. incompatibility: 01