Daikin EWWDC14DZXSA2 [42/47] High motor temperature alarm

Daikin EWWDC14DZXSA2 [42/47] High motor temperature alarm
D-EOMWC01405-18EN
42/47
EWWD_DZ EWWH_DZ
Bell icon is moving on controller’s display.
String in the alarm list:
CxCmp1 OffDischTmpHi
String in the alarm log:
CxCmp1 OffDischTmpHi
String in the alarm snapshot
CxCmp1 OffDischTmpHi
Check if the solenoid coil operates
properly
Check if the digital output operates
correctly.
Liquid injection orifice is small.
Check if when the liquid injection solenoid
is activated the temperature can be
controlled between the limits.
Check that the liquid injection line is not
obstructed by observing the discharge
temperature when it is activated.
Discharge temperature sensor could not
operate properly.
Check for proper operation of the
discharge temperature
Reset
Notes
Local HMI
Network
Auto
6.6.9 High Motor Current Alarm
This alarm indicates that the compressor absorbed current is exceeding a predefined limit.
Cause
Solution
The ambient temperature is too high (A/C
units) or condenser water temperature is
higher than the limit set on the unit
envelope (W/C units).
Check the unit selection to see if the unit
can operate at full load.
Check if all fans are operating properly and
are able to keep the condensing pressure
at the proper level (A/C units).
Clean condenser coils to allow a lower
condensing pressure (A/C units).
Check if condenser pump is operating
correctly, giving enough water flow (W/C
units).
Clean condenser water heat exchanger
(W/C units).
The wrong compressor model has been
selected.
Check the compressor model for this unit.
Notes
6.6.10 High Motor Temperature Alarm
This alarm indicates that the motor temperature has exceeded the maximum temperature limit for safe operations.
Symptom
Cause
Solution
Circuit status is Off.
The compressor does not load anymore or
even unload, circuit is stopped.
Bell icon is moving on controller’s display.
String in the alarm list:
CxCmp1 OffMotorTempHi
String in the alarm log:
CxCmp1 OffMotorTempHi
String in the alarm snapshot
CxCmp1 OffMotorTempHi
Insufficient motor cooling.
Check refrigerant charge.
Check if operational envelope of the unit is
respected.
Motor temperature sensor could not
operate properly.
Check the readings of the motor
temperature sensor and check the Ohmic
value. A correct reading should be around
hundreds of Ohm at ambient temperature.
Check the electrical connection of the
sensor with the electronic board.
Reset
Notes
Local HMI
Network
Auto
6.6.11 High Pressure alarm
This alarm is generated in case the Condensing saturated temperature rise above the Maximum condensing saturated
temperature and the control is not able to compensate to this condition. The maximum condenser saturated temperature
is 68.5°C but it can decrease when the evaporator saturated temperature become negative.
In case of water cooled chillers operating at high condenser water temperature, if the Condensing saturated temperature
exceeds the Maximum condenser saturated temperature, the circuit is only switched off without any notification on the
screen as this condition is considered acceptable in this range of operation.