Daikin EWWH740DZXEA3 [7/47] Using the controller

Daikin EWWD340DZXEA1 [7/47] Using the controller
EWWD_DZ EWWH_DZ
D-EOMWC01405-18EN
7/47
Controller/
Extension Module
Siemens Part
Number
Address
EWWD/H-VZ
Main Controller
POL687.00/MCQ
n/a
Extension Module
POL965.00/MCQ
2
EEXV Module 1
POL94U.00/MCQ
3
All boards are supplied from a common 24 Vac source. Extension boards can be directly powered by the Unit Controller.
All boards can be also supplied by a 24Vdc source.
CAUTION: Maintain the correct polarity when connecting the power supply to the boards, otherwise the peripheral
bus communication will not operate and the boards may be damaged.
2.5 Communication Modules
Any of the following modules can be connected directly to the left side of the main controller to allow a BAS or other remote
interface to function. Up to three can be connected to the controller at a time. The controller should automatically detect
and configure itself for new modules after booting up. Removing modules from the unit will require manually changing the
configuration.
Module
Siemens Part Number
Usage
BacNet/IP
POL908.00/MCQ
Optional
Lon
POL906.00/MCQ
Optional
Modbus
POL902.00/MCQ
Optional
BACnet/MSTP
POL904.00/MCQ
Optional
3 USING THE CONTROLLER
The standard HMI consists of an inbuilt display (A) with 3 buttons (B) and a push’n’roll control (C).
The keypad/display (A) consists of a 5-line by 22 character display. The function of the three buttons (B) is described
below:
Alarm status (from any page it links with the page with alarm list, alarm log and alarm snapshot if available)
Back to Main Page
Back to the previous level (it can be the Main Page)
The push’n’roll command (C) is used to scroll between the different menu pages, settings and data available on the HMI
for the active password level. Rotating the wheel allows to navigate between lines on a screen (page) and to increase and