2.14 Safety Valve
Each exchanger (evaporator and condenser) is provided with a safety valve installed on a changeover valve that allows
maintenance and periodic checks, without losing a significant amount of refrigerant. Do not leave the changeover device
in the intermediate position.
To prevent damages due to inhalation and direct contact with refrigerant gas, the safety valve outlets
must be connected with a conveyor pipe before operations. These pipes must be installed so that, in
case the valve opens, the discharged refrigerant flow not invest people and/or things, or can enter
the building through windows and/or other openings. The installer is responsible for connecting the
safety valve to the purge pipe and pipe dimensioning. In this regard, refer to the harmonized standard
EN13136 to dimension the drain pipes to be connected to the safety valves
2.15 Open the isolation and/or shut off valves
Before powering the machine and thus starting the compressors, open all valves that were closed at the factory for
shipping.
The valves to be opened are:
Valve (optional) installed on the discharge line.
Liquid line valve installed under the condenser.
Valve on the liquid injection line (inverter cooling).
Valve (optional) installed on the suction line.
2.16 Electrical connections
The unit must be connected with copper wire of adequate section, based on the maximum absorbed current indicated on
the unit label and in accordance with applicable electrical regulations.
Daikin Applied Europe S.p.A. cannot be held liable for improper electrical connections.
The connections to the terminals must be made with copper terminals and cables.
The electrical connection must be made by qualified personnel.
There is a risk of electric shock
The electrical panel must be connected keeping the correct phase sequence.
2.17 Phase imbalance
In a three-phase system, excessive imbalance between the phases is the cause of motor overheating. The maximum
allowed voltage imbalance is 2%, calculated as follows:
𝐼𝑚𝑏𝑎𝑙𝑎𝑛𝑐𝑒 % =
(
𝑉𝑥 𝑉𝑚
)
100
𝑉𝑚
Vx = phase with greatest imbalance
Vm = average of the voltages
I.e. the three phases measure 383, 386 and 392 volts respectively, the average is:
383+386+392
= 387 V
3
The percentage of imbalance is thus:
(392-387) x 100
= 1,29%
less than the maximum admitted (2%)
387
Before any maintenance and/or electrical connection to the compressor inverter, make sure the
system is turned off and the unit main switch open.
After turning off the main switch, wait at least 20 minutes for the inverter condensers to completely
discharge. Do not perform any maintenance and/or electrical connection in this period of time.
2.18 Control circuit
Each EWWD(H) VZ unit is factory tested. Both the control and power circuits undergo a careful functional test before the
machine is shipped.
The EWWD(H) VZ unit control circuit is powered at 230 Vac.
The controller ON/OFF switch (Q0) must be rotated to the OFF position whenever machine operations are not required.