Daikin EWWQ290L-SS [38/41] Technical specifications
![Daikin EWWQ290L-SS [38/41] Technical specifications](/views2/1677459/page38/bg26.png)
TECHNICAL SPECIFICATIONS
General The unit will be designed and manufactured in accordance with the following European directives:
• Construction of pressure vessel 97/23/EC (PED)
• Machinery Directive 2006/42/EC
• Low Voltage 2006/95/EC
• Electromagnetic Compatibility 2004/108/EC
• Electrical & Safety codes EN 60204–1 / EN 60335-2-40
• Manufacturing Quality Standards UNI – EN ISO 9001:2004
To avoid any losses, the unit will be tested at full load in the factory (at the nominal working conditions and water temperatures). The
chiller will be delivered to the job site completely assembled and charged with refrigerant and oil. The installation of the chiller must
comply with the manufacturer’s instructions for rigging and handling equipment.
The unit will be able to start up and operate (as standard) at full load with:
- evaporator leaving fluid temperature between ............... °C and ............... °C
- condenser leaving fluid temperature between ............... °C and ............... °C
Refrigerant Only HFC 410A can be used.
Performance The unit shall supply the following performances:
• Number : ............... unit(s)
• Cooling capacity for single unit : …………… kW
• Power input for single chiller in cooling mode : ............... kW
• Evaporator heat exchanger entering water temperature in cooling mode : ............... °C
• Evaporator heat exchanger leaving water temperature in cooling mode : ............... °C
• Evaporator heat exchanger water flow : ............... l/s
• Condenser heat exchanger entering water temperature in cooling mode : ............... °C
• Condenser heat exchanger leaving water temperature in cooling mode : ............... °C
• Condenser heat exchanger water flow : ............... l/s
Operating voltage range should be 400V ±10%, 3ph, 50Hz, voltage unbalance maximum 3%, without neutral conductor and shall only
have one power connection point.
Unit description The unit shall include as standard: one or two refrigerant circuit, two or four hermetic type rotary scroll
compressors (according to the capacity), electronic expansion device (EEXV), refrigerant direct expansion plate to plate heat
exchangers, R-410A refrigerant, motor starting components, control system and all components necessary for a safe and stable unit
operation.
The chiller will be factory assembled on a robust base frame made of galvanized steel, protected by an epoxy paint.
Sound level and vibrations Sound pressure level at 1 meter distance in free field, hemispheric conditions, shall not exceed
………dB(A). The sound pressure levels must be rated in accordance to ISO 3744 (other types of rating can not be used).
Vibration on the base frame should not exceed 2 mm/s.
Dimensions Unit dimensions shall not exceed following indications:
- Unit length ............... mm
- Unit width ............... mm
- Unit height ............... mm
Compressors The units shall be equipped with:
• High performance hermetic scroll compressors optimized to work with R410a, with reduced vibration and sound emissions. High
efficiency values shall be guaranteed:
-by high volumetric efficiency in the whole range of application, through the continuous contact between the fixed and the orbiting
scroll deleting the dead space and the re-expansion of the refrigerant gas;
-by low pressure drops due to the absence of inlet and discharge valves and to the uniform compression cycle;
-reduction of the heat exchange between the gas during suction and discharge due to the separation of gas flows;
•The reduced noise shall be obtained: -for the absence of the inlet and discharge valves
-for the uniform compression cycle
-for the absence of pistons which ensures reduced vibration and pulsation of the refrigerant
• The engine shall be cooled by the suction refrigerant fluid.
• The terminal shall be contained in a casing with protection degree IP 54.
• The compressors shall be provided with crankcase heater to prevent the dilution of refrigerant and oil the during the stops of the unit;
• Shall be present an electronic thermal protection for the three phases complete with sensors on the stator windings to avoid
overheating caused by lack of phase, insufficient cooling, mechanical locks, power supply out of tolerance;
•The compressors shall be connected in Tandem on a single refrigerating circuit.
•The compressors shall be fitted on rubber antivibration mounts.
•The compressors shall be provided complete with oil charge.
Page 38 of 41
Содержание
- Databook 1
- Ewwq g l 1
- Performance according to en14511 1
- Water cooled chiller cooling 1
- Certifications 2
- Code requirements safety and observant of laws directives 2
- Compact design 2
- Features and benefits 2
- Flexibility 2
- Low operating cost and extended operating life 2
- Page 2 of 41 2
- Plug play installation 2
- Superior control logic 2
- Versions 2
- Wide capacity range 2
- Wide operating range 2
- Features and benefits 3
- Page 3 of 41 3
- Sound configurations 3
- Cabinet and structure 4
- Compressor 4
- Condenser plate heat exchanger 4
- Electrical control panel 4
- Electronic expansion valve 4
- Evaporator plate heat exchanger 4
- General characteristics 4
- Page 4 of 41 4
- Power section the power section includes compressors protection devices compressors starters and control circuit power supply 4
- Refrigerant 4
- Refrigerant circuit 4
- Unit controller unit controller is installed as standard it can be used to modify unit set points and check control parameters a built in display shows chiller operating status plus temperatures and pressures of water refrigerant programmable values set points a sophisticated software with predictive logic selects the most energy efficient combination of compressors and eexv to keep stable operating conditions to maximise chiller energy efficiency and reliability the unit controller is able to protect critical components based on external signs from its system such as motor temperatures refrigerant gas and oil pressures correct phase sequence pressure switches and evaporator the input coming from the high pressure switch cuts all digital output from the controller in less than 50ms this is an additional security for the equipment fast program cycle 200ms for a precise monitoring of the system floating point calculations supported for increased accuracy in pressure temperature conversio 4
- General characteristics 5
- Page 5 of 41 5
- Supervising systems on request 5
- General characteristics 6
- Options 7
- Options on request 7
- Page 7 of 41 7
- Standard options supplied on basic unit 7
- Options 8
- Page 8 of 41 8
- Capacity class in kw cooling 9
- Efficiency level 9
- Inverter 9
- Machine type 9
- Model series 9
- Nomenclature 9
- Page 9 of 41 9
- Refrigerant 9
- Sound level 9
- Ewwq g ss 10
- Page 10 of 41 10
- Technical specifications 10
- Ewwq g ss 11
- Page 11 of 41 11
- Technical specifications 11
- Ewwq l ss 12
- Page 12 of 41 12
- Technical specifications 12
- Ewwq l ss 13
- Page 13 of 41 13
- Technical specifications 13
- Electrical specifications 14
- Ewwq g ss 14
- Page 14 of 41 14
- Electrical specifications 15
- Ewwq l ss 15
- Page 15 of 41 15
- Ewwq g ss 16
- Ewwq l ss 16
- Page 16 of 41 16
- Sound levels 16
- Ewwq g ss 17
- Ewwq l ss 17
- Page 17 of 41 17
- Sound level at distance 17
- Operating limits 18
- Page 18 of 41 18
- Table 1 water heat exchanger minimum and maximum water δt 18
- Table 2 water heat exchanger evaporator fouling factors 18
- Operating limits 19
- Page 19 of 41 19
- Table 2 water heat exchanger condenser fouling factors 19
- Water content in cooling circuits 19
- Cooling performance 21
- Ewwq g ss 21
- Page 21 of 41 21
- Cooling performance 22
- Ewwq g ss 22
- Page 22 of 41 22
- Cooling performance 23
- Ewwq g ss 23
- Page 23 of 41 23
- Cooling performance 24
- Ewwq g ss 24
- Page 24 of 41 24
- Cooling performance 25
- Ewwq g ss 25
- Page 25 of 41 25
- Cooling performance 26
- Ewwq g ss 26
- Page 26 of 41 26
- Cooling performance 27
- Ewwq l ss 27
- Page 27 of 41 27
- Cooling performance 28
- Ewwq l ss 28
- Page 28 of 41 28
- Cooling performance 29
- Ewwq l ss 29
- Page 29 of 41 29
- Cooling performance 30
- Ewwq l ss 30
- Page 30 of 41 30
- Cooling performance 31
- Ewwq l ss 31
- Page 31 of 41 31
- Cooling performance 32
- Ewwq l ss 32
- Page 32 of 41 32
- Cooling performance 33
- Ewwq l ss 33
- Page 33 of 41 33
- C f e d 35
- Dimensional drawing 35
- Legend 35
- M l i h g b o 35
- Page 35 of 41 35
- C f e d 36
- Dimensional drawing 36
- Legend 36
- M l i h g b o 36
- Page 36 of 41 36
- Acoustic protection 37
- Handling 37
- Installation notes 37
- Location 37
- Page 37 of 41 37
- Space requirements 37
- Storage 37
- Warning 37
- Compressors 38
- Dimensions 38
- General 38
- Page 38 of 41 38
- Performance 38
- Refrigerant 38
- Sound level and vibrations 38
- Technical specifications 38
- Unit description 38
- Condensation control 39
- Condenser phe 39
- Controller 39
- Controller main features 39
- Electrical control panel 39
- Evaporator phe 39
- Hydronic kit options on request 39
- Page 39 of 41 39
- Refrigerant circuit 39
- Technical specifications 39
- High level communications interface on request 40
- Page 40 of 41 40
- Technical specifications 40
Похожие устройства
- Daikin EWWQ290L-SS Инструкция по монтажу
- Daikin EWWQ290L-SS Инструкция по эксплуатации
- Daikin EWWQ330L-SS Технические данные
- Daikin EWWQ330L-SS Инструкция по монтажу
- Daikin EWWQ330L-SS Инструкция по эксплуатации
- Daikin EWWQ380L-SS Технические данные
- Daikin EWWQ380L-SS Инструкция по монтажу
- Daikin EWWQ380L-SS Инструкция по эксплуатации
- Daikin EWWQ430L-SS Технические данные
- Daikin EWWQ430L-SS Инструкция по монтажу
- Daikin EWWQ430L-SS Инструкция по эксплуатации
- Daikin EWWQ480L-SS Инструкция по монтажу
- Daikin EWWQ480L-SS Технические данные
- Daikin EWWQ480L-SS Инструкция по эксплуатации
- Daikin EWWQ540L-SS Технические данные
- Daikin EWWQ540L-SS Инструкция по эксплуатации
- Daikin EWWQ540L-SS Инструкция по монтажу
- Daikin EWWQ600L-SS Технические данные
- Daikin EWWQ600L-SS Инструкция по эксплуатации
- Daikin EWWQ600L-SS Инструкция по монтажу