Technical details - EWYD-4ZA
Air to Water mode
Cooling only EWYD-4ZXSA2 400 450 500 550 600 650 700 800 900 C10 C11 C12 C13 C14
Cooling capacity Nom. Gross Value kW 403 453 504 552 604 655 705 804 903 1003 1103 1207 1307 1429
EER Gross Value 3,19 3,28 3,27 3,28 3,27 3,23 3,41 3,39 3,32 3,30 3,35 3,31 3,34 3,20
Cooling capacity Nom. Net Value kW 402 452 503 551 602 654 703 802 901 1001 1101 1204 1303 1423
EER Net Value 3,17 3,25 3,25 3,25 3,24 3,19 3,37 3,36 3,28 3,27 3,32 3,28 3,29 3,15
Air to Water mode
Heating only EWYD-4ZXSA2 400 450 500 550 600 650 700 800 900 C10 C11 C12 C13 C14
Heating capacity Nom. Gross Value kW 402 453 502 549 599 653 701 800 899 1001 1099 1199 1307 1423
COP Gross Value 3,34 3,53 3,47 3,49 3,47 3,40 3,58 3,57 3,58 3,55 3,64 3,59 3,46 3,48
Heating capacity Nom. Net Value kW 403 453 504 551 601 655 702 803 902 1003 1102 1202 1312 1429
COP Net Value 3,33 3,52 3,45 3,47 3,45 3,38 3,55 3,54 3,55 3,53 3,62 3,56 3,43 3,45
Water to Water mode
Heating + Cooling EWYD-4ZXSA2 400 450 500 550 600 650 700 800 900 C10 C11 C12 C13 C14
Cooling capacity Nom. Gross Value kW 314 356 395 432 476 513 551 632 708 794 869 950 1028 1120
Heating capacity Nom. Gross Value kW 402 454 502 548 602 651 702 801 895 997 1095 1202 1299 1421
TER Gross Value 8,14 8,32 8,35 8,43 8,57 8,44 8,30 8,47 8,57 8,82 8,72 8,55 8,59 8,44
Cooling capacity Nom. Net Value kW 313 356 394 430 475 511 549 630 705 792 867 947 1023 1114
Heating capacity Nom. Net Value kW 402 455 503 549 603 653 704 803 898 999 1097 1205 1303 1426
TER Net Value 8,03 8,19 8,19 8,24 8,38 8,23 8,10 8,26 8,34 8,65 8,52 8,33 8,31 8,13
Dimensions Unit Height mm 2455
Width mm 2240
Depth mm 5775 5775 6675 6675 7575 8475 8475 8475 9425 10375 11325 12275 13225 14175
Cold Water heat
exchanger
Type Single pass shell & tube
Water ow rate Cooling Nom. l/s 19,2 21,6 24,0 26,3 28,8 31,3 33,6 38,3 43,1 47,8 52,6 57,6 62,4 68,2
Water pressure drop Cooling Nom. kPa 13,7 16,9 20,5 31,4 28,0 32,7 33,9 31,5 38,9 26,4 31,3 36,4 51,9 62,5
Water volume l 149 149 262 240 298 298 307 280 280 481 481 481 451 451
Hot Water heat
exchanger
Type Single pass shell & tube
Water ow rate Heating Nom. l/s 19,4 21,9 24,3 26,6 29,0 31,6 33,9 38,7 43,5 48,4 53,2 58,0 63,2 68,8
Water pressure drop Heating Nom. kPa 13,0 16,1 23,9 27,6 30,0 35,3 32,8 42,5
37,4 23,4 34,4 40,2 48,7 55,8
Water volume l 149 149 240 240 280 280 298 298 280 481 451 451 451 451
Air heat exchanger Type Fins & tubes
Compressor Type Inverter driven single screw compressor
Quantity 2
Fan Type Direct propeller, Inverter driven
Quantity 10 10 12 12 14 16 16 16 18 20 22 24 26 30
Sound power level Cooling Nom. dBA 99 98 99 99 100 100 102 102 102 103 103 103 103 104
Sound pressure
level @ 1 m
Cooling Nom. dBA 78 77 77 78 78 79 80 80 80 80 80 80 80 81
Operation range Air side Cooling Min.~Max. °CDB -18°C / +50°C
Water side Cooling Min.~Max. °CDB -8°C / +20°C
Air side Heating Min.~Max. °CDB -15°C / +50°C
Water side Heating Min.~Max. °CDB +30°C / +61°C
Refrigerant Type / GWP R134a / 1430
Circuits Quantity 2
Power supply Phase/Frequency/Voltage Hz/V 3~/50/400 ~ 3/60/380
Notes:
Performances are based on the following conditions:
Air to water, Cooling only: Cold Water Heat Exchanger 12/7°C; ambient 35°C. unit at full load operation; operating uid: water
Air to water, Heating only: Hot Water Heat Exchanger 40/45°C; ambient 7°C; unit at full load operation; operating uid water
Water to water, Cooling + Heating: Cold water Heat Exchanger */7°C; Hot Water Heat Exchanger */45°C; operating uid water
Sound levels refer to the unit in Cooling only mode in nominal conditions
Data are subject to change without any notice
Содержание
- Ewyd 4z 1
- Full inverter technology the best choice for every application 3
- Top class efficiency 3
- Why choose 3
- Z multipurpose series 3
- Application flexibility 2 4
- Extra capacity in boosted operation 4
- In case of power failure daikin 4z is able to restart in less than 30 sec the ups installed in electrical box keeps the unit controller always powered is also possible to give if needed priority to restore the cooling or the heating load 4
- Rapid restart functionality 4
- Thanks to the variable speed drive of the compressor is possible to benefit of an extra capacity during the coldest days in winter or the hottest days in summer 4
- Wide operating envelope for cooling and heating 4
- Best solution for simultaneous cooling and heating 3 5
- Big multipurpose buildings hotels hospital are just a few examples of application for multipurpose units 5
- Load profile with simultaneous request for cooling and heating 5
- Lower energy consumption compared to traditional systems 5
- Same cooling and heating energy delivered with 30 energy consumption 5
- Technical details ewyd 4za 6
- Technical details ewyd 4za 7
- Comfort cooling application 8
- Daikin europe n v naamloze vennootschap zandvoordestraat 300 8400 oostende belgium www daikin eu be 0412 120 336 rpr oostende responsible editor 8
- Hospital application 8
- Process cooling application 8
Похожие устройства
- Daikin EWYD8004ZXLA2 Инструкция по монтажу
- Daikin EWYD8004ZXLA2 Брошюра
- Daikin EWYD4004ZXRA2 Брошюра
- Daikin EWYD4004ZXRA2 Инструкция по монтажу
- Daikin EWYD4504ZXRA2 Инструкция по монтажу
- Daikin EWYD4504ZXRA2 Брошюра
- Daikin EWYD5004ZXRA2 Инструкция по монтажу
- Daikin EWYD5004ZXRA2 Брошюра
- Daikin EWYD5504ZXRA2 Инструкция по монтажу
- Daikin EWYD5504ZXRA2 Брошюра
- Daikin EWYD6004ZXRA2 Инструкция по монтажу
- Daikin EWYD6004ZXRA2 Брошюра
- Daikin EWYD6504ZXRA2 Инструкция по монтажу
- Daikin EWYD6504ZXRA2 Брошюра
- Daikin EWYD7004ZXRA2 Брошюра
- Daikin EWYD7004ZXRA2 Инструкция по монтажу
- Daikin EWYD8004ZXRA2 Инструкция по монтажу
- Daikin EWYD8004ZXRA2 Брошюра
- Daikin EWYD4004ZXSA2 Брошюра
- Daikin EWYD4004ZXSA2 Инструкция по монтажу