MEAN WELL MSP-100-48 Data sheet онлайн

MEAN WELL MSP-100-3.3 Data sheet онлайн
Universal AC input / Full range
Built-in active PFC function
High efficiency up to 90%
Withstand 300VAC surge input for 5 seconds
Protections: Short circuit / Overload / Over voltage
Protections: Over temperature (optional)
Cooling by free air convection
1U low profile 38mm
Medical safety approved (MOOP level)
Built-in remote ON-OFF control
No load power consumption<0.5W
All using 105 long life electrolytic capacitors
5 years warranty
SPECIFICATION
MSP-100-3.3 MSP-100-5 MSP-100-7.5 MSP-100-12 MSP-100-15 MSP-100-24 MSP-100-36 MSP-100-48
MODEL
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
RIPPLE & NOISE (max.)
Note.2
OUTPUT VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE
Note.3
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
Note.5
FREQUENCY RANGE
POWER FACTOR (Typ.)
EFFICIENCY (Typ.)
INPUT
ENVIRONMENT
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT Note.6
OVER TEMPERATURE
SAFETY STANDARDS
SAFETY &
EMC
(Note 4)
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
WORKING TEMP.
REMOTE CONTROL
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MTBF
DIMENSIONOTHERS
NOTE
PACKING
OVERLOAD
OVER VOLTAGE
PROTECTION
AC CURRENT (Typ.)
3.3V 5V 7.5V 12V 15V 24V 36V 48V
20A 17A 13.5A 8.5A 7A 4.5A 2.9A 2.2A
0 ~ 20A 0 ~ 17A 0 ~ 13.5A 0 ~ 8.5A 0 ~ 7A 0 ~ 4.5A 0 ~ 2.9A 0 ~ 2.2A
66W 85W 101.3W 102W 105W 108W 104.4W 105.6W
80mVp-p 80mVp-p 100mVp-p 120mVp-p 150mVp-p 150mVp-p 200mVp-p 240mVp-p
3.1 ~ 3.8V 4.75 ~ 5.8V 7.1 ~ 9V 11.4 ~ 13.8V 14.25 ~ 18V 22.8 ~ 28.8V 34.2 ~ 39.6V 45.6 ~ 55.2V
±0.5% ±0.5% ±0.5% ±0.3% ±0.3% ±0.2% ±0.2% ±0.2%
±2.0% ±2.0% ±1.5% ±0.8% ±0.8% ±0.5% ±0.5% ±0.5%
2500ms, 100ms/230VAC 2500ms, 100ms/115VAC at full load
50ms/230VAC 20ms/115VAC at full load
85 ~ 264VAC 120 ~ 370VDC
47 ~ 63Hz
PF>0.95/230VAC PF>0.98/115VAC at full load
78% 83%
6 ~ 7V 9.4 ~ 10.9V 14.4 ~ 16.8V 18.8 ~ 21.8V 30 ~ 34.8V 41.4 ~ 48.6V 57.6 ~ 67.2V
84% 87.5% 88% 88.5% 89% 90%
1.2A/115VAC 0.6A/230VAC
35A/115VAC 65A/230VAC
105 ~ 135% rated output power
Protection type : Constant current limiting for Vo=50 ~ 100% of rated voltage, recovers automatically after fault condition is removed
3.96 ~ 4.62V
Protection type : Shut down o/p voltage, re-power on to recover
Shut down o/p voltage, recovers automatically after temperature goes down
I/P-O/P:4KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
-40 ~ +60 (Refer to "Derating Curve")
RC+/RC- : 0 ~ 0.8V= power on ; 4 ~ 10V = power off
20 ~ 90% RH non-condensing
-40 ~ +85 , 10 ~ 95% RH
± 0.04%/ (0 ~ 50 )
10 ~ 500Hz, 5G 10min./1cycle, 60min. each along X, Y, Z axes
295.7K hrs min. MIL-HDBK-217F (25 )
159*97*38mm (L*W*H)
Fi le Name:MSP-100-SPEC 2014-12-08
Features :
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.
(as available on http://www.meanwell.com)
5. Derating may be needed under low input voltages. Please check the derating curve for more details.
6. Touch current was measured from primary input to DC output.
7. When the input voltage is less than 40VAC, the SPS may exhibit degradation of performance. The final product manufacturers must re-confirm this
deviation that does not affect basic safety or essential performance.
MSP-10 0
seri e s
100W Single Output Medical Type
FUNCTION
0.38Kg; 24pcs/10.1Kg/0.76CUFT
+2.5,-3.5% +2.5,-3.5% ±2.5% ±1.5% ±1.5% ±1.5% ±1.5% ±1.5%
EMC IMMUNITY
EMC EMISSION
ANSI/AAMI ES60601-1, IEC60601-1 approved
Compliance to EN55011 (CISPR11) Class B, EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11, EN60601-1-2
Earth leakage current < 300 A/264VAC , Touch leakage current < 100 A/264VAC
μ
μ
ISOLATION LEVEL
Primary-Secondary: 2×MOOP, Primary-Earth: 1×MOOP, Secondary-Earth: 1×MOOP