MEAN WELL MSP-600-36 [3/4] Msp 600

MEAN WELL MSP-600-5 [3/4] Msp 600
The remote sensing compensates voltage drop on
the load wiring up to 0.5V.
10
10
9
9
CN100
AUX
RC-
GND
GND
-S
AUXG
RC+
CS
DC-OK
+S
2
2
1
1
1.Remote Sense
1
1
9
9
10
10
Sense lines should
be tw isted in pairs
LOAD
-
+
+S -S
(Pin9) (Pin10)
Fig 1.1
Between DC-OK(pin7) and GND(pin6,8)
3.3 ~ 5.6V
0 ~ 1V
Output Status
ON
OFF
DC-OK signal is a TTL level signal. High when PSU turns on.
CN100
AUX
RC-
GND
GND
-S
AUXG
RC+
CS
DC-OK
+S
2.DC-OK Signal
Fig 2.1
CN100
CN100
2
2
5 CS
Current sharing signal. When units are connected in parallel, the CS pins of the units should be connected to allow current balance
between units.
7 DC-OK
DC-OK signal is a TTL level signal, referenced to pin8(DC-OK GND). High when PSU turns on.
9 +S
Positive sensing. The +S signal should be connected to the positive terminal of the load. The +S and -S leads should be twisted in pair to
minimize noise pick-up effect. The maximum line drop compensation is 0.5V.
10 -S
Negative sensing. The -S signal should be connected to the negative terminal of the load. The -S and +S leads should be twisted in pair to
minimize noise pick-up effect. The maximum line drop compensation is 0.5V.
6,8 GND
This pin connects to the negative terminal(-V). Return for DC-OK signal output.
600W Single Output Medical Type
Fi le Name:M SP-600-SPEC 2014-12-08
MSP-60 0
seri e s
Function Description of CN100
Pin No. Function
Description
Function Manual
3
4
RC+
RC-
Remote control ground.
Turns the output on and off by electrical or dry contact between pin 4 (RC-), Short: Power OFF, Open: Power ON.
2
1
AUX
AUXG
Auxiliary voltage output, 4.75~5.25V, referenced to pin 1(AUXG). The maximum load current is 0.3A. This output has the built-in oring
diodes and is not controlled by the "remote ON/OFF control".
Auxiliary voltage output ground. The signal return is isolated from the output terminals (+V & -V).