Daikin EWYT400B-XSA2-VFDFAN [66/75] Water filter pressure drops

Daikin EWYT085B-XLA1 [66/75] Water filter pressure drops
INSTALLATIONS NOTES
66 | 75
Water filter pressure drops
Soft Starter Values of the Inrush Current, in case of soft starter selected, are showed here below in the
table. The vaues are calculated in case of the biggest compressor switching on with all the other compressors
and fans on.
Model
Inrush
Current
with Soft
Starter
[A]
Model
Inrush
Current
with Soft
Starter
[A]
Model
Inrush
Current
with Soft
Starter
[A]
EWYT085B-SS(L)(R)A1
143
EWYT300B-SS(L)(R)A2
420
EWYT310B-XRA2
428
EWYT105B-SS(L)(R)A1
196
EWYT340B-SS(L)(R)A2
454
EWYT350B-XRA2
462
EWYT135B-SS(L)(R)A1
212
EWYT390B-SS(L)(R)A2
492
EWYT400B-XRA2
496
EWYT175B-SS(L)(R)A1
317
EWYT430B-SS(L)(R)A2
522
EWYT440B-XRA2
530
EWYT215B-SS(L)(R)A1
349
EWYT490B-SS(L)(R)A2
568
EWYT500B-XRA2
580
EWYT205B-SS(L)(R)A2
276
EWYT540B-SS(L)(R)A2
613
EWYT560B-XRA2
629
EWYT235B-SS(L)(R)A2
293
EWYT590B-SS(L)(R)A2
651
EWYT600B-XRA2
663
EWYT255B-SS(L)(R)A2
307
EWYT630B-SS(L)(R)A2
681
EWYT630B-XRA2
697
EWYT650B-XRA2
697
EWYT085B-XS(L)(R)A1
145
EWYT310B-XS(L)A2
418
EWYT115B-XS(L)(R)A1
198
EWYT350B-XS(L)A2
450
EWYT135B-XS(L)(R)A1
212
EWYT400B-XS(L)A2
483
EWYT175B-XS(L)(R)A1
319
EWYT440B-XS(L)A2
515
EWYT215B-XS(L)(R)A1
351
EWYT500B-XS(L)A2
563
EWYT215B-XS(L)(R)A2
280
EWYT560B-XS(L)A2
611
EWYT235B-XS(L)(R)A2
296
EWYT600B-XS(L)A2
644
EWYT265B-XS(L)(R)A2
311
EWYT630B-XS(L)A2
676
EWYT650B-XS(L)A2
697
0
50
100
150
0 5 10 15 20 25 30 35 40
External pressure head [kPa]
Water flow [l/s]
Water filter pressure drops
2.5"
3"
4"

Содержание

Скачать