Daikin EWYT500B-XSA2-VFDFAN [42/75] Electrical specification

Daikin EWYT350B-XLA2 [42/75] Electrical specification
42 | 75
ELECTRICAL SPECIFICATION
EWYT~B-SR
MODEL
EWYT085B-
SRA1
EWYT105B-
SRA1
EWYT135B-
SRA1
EWYT175B-
SRA1
EWYT205B-
SRA2
EWYT215B-
SRA1
POWER SUPPLY
Phases
3
3
3
3
3
3
Frequency
50
50
50
50
50
50
Voltage
400
400
400
400
400
400
Voltage tolerance Minimum
-10%
-10%
-10%
-10%
-10%
-10%
Voltage tolerance Maximum
10%
10%
10%
10%
10%
10%
UNIT
Maximum inrush current
211
327
343
464
408
495
Nominal running current cooling
55
67
77
101
128
126
Maximum running current
68
85
101
131
166
163
Maximum current for wires sizing
75
94
111
144
183
179
FANS
Nominal running current cooling
4
6
8
8
9
9
COMPRESSORS
Phases
3
3
3
3
3
3
Voltage
400
400
400
400
400
400
Voltage tolerance Minimum
-10%
-10%
-10%
-10%
-10%
-10%
Voltage tolerance Maximum
10%
10%
10%
10%
10%
10%
Maximum running current
64
92
89
146
184
151
Starting method
DOL
DOL
DOL
DOL
DOL
DOL
MODEL
EWYT235B-
SRA2
EWYT255B-
SRA2
EWYT300B-
SRA2
EWYT340B-
SRA2
EWYT390B-
SRA2
POWER SUPPLY
Phases
No.
3
3
3
3
3
Frequency
Hz
50
50
50
50
50
Voltage
V
400
400
400
400
400
Voltage tolerance Minimum
%
-10%
-10%
-10%
-10%
-10%
Voltage tolerance Maximum
%
10%
10%
10%
10%
10%
UNIT
Maximum inrush current
A
425
439
564
598
636
Nominal running current cooling
A
136
149
173
196
223
Maximum running current
A
183
197
232
266
304
Maximum current for wires sizing
A
201
217
255
292
334
FANS
Nominal running current cooling
A
11
11
11
13
18
COMPRESSORS
Phases
No.
3
3
3
3
3
Voltage
V
400
400
400
400
400
Voltage tolerance Minimum
%
-10%
-10%
-10%
-10%
-10%
Voltage tolerance Maximum
%
10%
10%
10%
10%
10%
Maximum running current
A
181
177
235
292
297
Starting method
DOL
DOL
DOL
DOL
DOL

Содержание

Скачать