Daikin EWYT175B-SSA1 [15/75] Installation options on request

Daikin EWYT135B-SSA1 [15/75] Installation options on request
15 | 75
OPTIONS
- Set a “thermostat off” pump speed. Providing the unit with the inverter kit for the on-board pump is
possible to manage two different water flow settings. A setting for water flow during the "Thermostat ON" mode
(when the unit is actually providing cooling to the plant), and a set for the “thermostat off” mode (when the
plant load is satisfied and the compressors are waiting to start). This feature allows to achieve energy saving
on plant operating cost by reducing the speed of the pumps when the unit has reached the set point.
Max Ambient temperature for a proper working of the Inverters is 40°C.
Daikin on site modem with antenna (opt. code 155)
Whenever LAN connection to the unit will not be available, connecting the unit to Daikin on Site will be possible
through a dedicated 3G M2M modem that can be ordered from Factory. When ordered, the modem will be
installed on the unit before leaving the Factory.
Heating only mode (opt. code 188)
Allowing the unit to operate in heating mode only. Cooling mode operation is not supported.
Installation options On request
Rubber anti vibration mounts (opt. code 75) - option incompatibility 77.
Shipped loose, rubbe mounts are to be positioned under the base frame of the unit during installation. Ideal to
reduce the vibrations when the unit is floor mounted.
Spring anti vibration mounts (opt. code 77) - option incompatibility 75.
Shipped loose, spring mounts are to be positioned under the base frame of the unit during installation. Ideal for
dampening vibrations for installation on roofs and metallic structures.
External tank without cabinet 500 L (opt. code 83)
Inertial tank for chilled water storage - option incompatibility 84-87-88.
External tank without cabinet 1000 L (opt. code 84)
Inertial tank for chilled water storage - option incompatibility 83-87-88.
External tank with cabinet 500 L (opt. code 87)
Inertial tank for chilled water storage with cabinet - option incompatibility 83-84-88.
External tank with cabinet 1000 L (opt. code 88)
Inertial tank for chilled water storage with cabinet - option incompatibility 83-84-87.
Other options On request
Container kit (opt. code 71)
Specific solution designed to facilitate loading/unloading of the unit into the container and to reduce risk of
damage. - option incompatibility 112.
Transport kit (opt. code 112)
Specific solution that offers shocks’ absorption during unit transportation. - option incompatibility 71.