Daikin EWYT560B-XRA2 [38/75] Technical al specification

Daikin EWYT630B-SLA2-VFDFAN [38/75] Technical al specification
38 | 75
TECHNICAL AL SPECIFICATION
MODEL
EWYT235B-
XRA2
EWYT265B-
XRA2
EWYT310B-
XRA2
EWYT350B-
XRA2
HEATING PERFORMANCE
Capacity - Heating
237.57
256.58
301.04
344.8
Unit power input - Heating
68.99
75.49
86.19
98.95
COP
3.443
3.399
3.493
3.485
SCOP
3.82
3.81
4.06
4.01
HEAT EXCHANGER -
EVAPORATOR
Water temperature in
40
40
40
40
Water temperature out
45
45
45
45
FAN
Air Temperature
7
7
7
7
MODEL
EWYT400B-
XRA2
EWYT440B-
XRA2
EWYT500B-
XRA2
EWYT560B-
XRA2
EWYT600B-
XRA2
EWYT630B-
XRA2
EWYT650B-
XRA2
HEATING
PERFORMANCE
Capacity - Heating
kW
395.81
438.23
494.13
549.6
588.57
620.71
637.4
Unit power input - Heating
kW
114.46
124.61
143.5
161.2
175.33
186.93
193.22
COP
3.458
3.517
3.443
3.409
3.357
3.321
3.299
SCOP
3.95
4.03
3.99
4.04
4
3.98
3.88
HEAT EXCHANGER -
EVAPORATOR
Water temperature in
°C
40
40
40
40
40
40
40
Water temperature out
°C
45
45
45
45
45
45
45
FAN
Air Temperature
7
7
7
7
7
7
7
All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: 12,0/7,0°C;
ambient 35,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018
All the performances (Heating capacity, unit power input in heating and COP) are based on the following conditions:
40,0/45,0°C; ambient 7,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018
SCOP is based on the following conditions: Tbivalent -5 °C, Tdesign -10 °C, Average ambient conditions, Ref. EN14825. In
accordance with standard EN14825, comfort low temperature, average climate, SEER and µs values applicable Ecodesign
regulation: (EU) No 2016/2281;
* PHE: Plate Heat Exchanger; S&T: Single Pass Shell & Tube; MCH: Microchannel; DPT: Direct Propeller Type; DOL: Direct On
Line - VFD: Inverter
** Sound power level (referred to 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and
Eurovent 8/1 for Eurovent certified units. The certification refers only to the overall sound power level, the sound pressure is
calculated from the sound power level and are for information only and not considered binding.
The minimum capacity indicated is referred to unit operating at standard Eurovent conditions.
Dimensions and weights are for indication only and not considered binding. Before designing the installation, consult the official
drawings available from the factory at request.
All the data are referred to standard unit without options. All data are subject to change without notice
The values of the Pressure Drops refers to the pressure drops in the Water heat exchanger only.