5.Select Overload Protection Type
(2)Remove the shorting connector on CN3 that is shown in Fig 5.1, the Overload Protection Type will be "continuous constant current limiting".
Overload Protection Type : constant current limiting
Overload Protection Type : constant current limiting with delay shutdown after 5 seconds
6.Current Sharing with Remote Sense
(1)Insert the shorting connector on CN3 that is shown in Fig 5.2, the Overload Protection Type will be "constant current limiting with delay shutdown after 5 seconds,
re-power on to recover". This is the factory default.
File Name:RSP-3000-SPEC 2017-07-14
3000W Power Supply with Single Output
RSP-3000 series
RSP-3000 has the built-in active current sharing function and can be connected in parallel, up to 3 units, to provide higher output power as exhibited below :
Difference of output voltages among parallel units should be less than 0.2V.
The total output current must not exceed the value determined by the following equation:
Maximum output current at parallel operation=(Rated current per unit) (Number of unit) 0.9××
The power supplies should be paralleled using short and large diameter wiring and then connected to the load.
×When the total output current is less than 3% of the total rated current, or say (3% of Rated current per unit) (Number of unit)
the current shared among units may not be fully balanced.
+S,-S CSand on CN1 or CN2are connected mutually in parallel.
Under parallel operation, the "output voltage programming" function is not available.
No.1(Master)
No.2(Slave)
No.3(Slave)
Load
+V
-V
+S
-S
-V
-V
-V
+V
+V
+V
AC/L
AC/L
AC/L
AC/N
AC/N
AC/N
Sense lines should be twisted in pairs to minimize noise pick-up.
When remote sensing is used in parallel operation, the sensing wire must be
connected only to the master unit