When activated, they reset automatically, but the controller
needs to be reset manually.
Low pressure safety
(circuit safety device)
When the suction pressure of a circuit is too low, the circuit
controller shuts down the circuit. When the pressure returns to
normal, the safety device can be reset on the controller.
Reverse phase protector (general safety device)
The reverse phase protector (R1P) is installed in the main
switch box of the unit. It prevents the compressors from running
in the wrong direction. If the unit does not start, two phases of
the power supply must be inverted.
Discharge thermal protector (circuit safety device)
The discharge thermal protectors (Q*D) are activated when the
temperature of the refrigerant leaving the compressor becomes
too high. When the temperature returns to normal, the protector
resets automatically, but the controller needs to be reset
manually.
Outlet water temperature sensors (circuit safety device)
The outlet water temperature sensors (R4~6T) measure the
temperature of the water at the water heat exchanger outlet.
The protection device shuts down the circuit when the
temperature of the chilled water becomes too low in order to
prevent freezing of the water during operation.
When the outlet water temperature returns to normal, the
protector resets automatically.
Additional interlock contact (general safety device)
To avoid that the unit could be started or run without water
circulating through the water heat exchanger, an interlock
contact (S10L) of e.g. a flow switch must be switched in the
start-up circuit of the unit.
Fan motor thermal protector (part safety device)
The fan motors are equipped with thermal protectors (Q*F).
The protectors are activated when the temperature becomes
too high. When temperature returns to normal, the protector
resets automatically.
Measuring devices
Checking the high and low pressure of the refrigerant circuit is
necessary to ensure the proper operation of the unit and to
guarantee that the rated output will be obtained. The unit can
therefore be equipped with an optional high and low pressure
gauge. Refer to "Switching the unit on" for the acceptable pressures.
High pressure gauge
The high pressure gauge indicates the discharge pressure
(pressure at the outlet of the compressor).
Low pressure gauge
The low pressure gauge indicates the suction pressure
(pressure at the inlet of the compressor).
Internal wiring - Parts table
Refer to the internal wiring diagram supplied with the unit. The
abbreviations used are listed below:
C1~6 .............. Capacitors for fanmotors
E1,2,3H ......... Crankcase heater
F1,2,3U.......... Fuses (field supply)
F5B ................ Fuse for primary of TR1
F6B ................ Fuse for secondary of TR1
F7B ................ Fuse for fan circuit + control circuit
H1P ............... Indication lamp alarm (field supply)
H2P ............... Indication lamp general operation (field supply)
H3,4,5P ......... Indication lamp operation of compressor (field supply)
J1,2 ............... Connector for analog input
J3,4,21 .......... Connector for digital input
J5,6,22,24 ..... Connector for digital output
J17 ................ Connector for power supply of controller
K1,2,3M ........ Compressor contactor
K4,5,6S ......... Over current relay
K1,2,3A ......... Auxiliary relay for safety
K4A ............... Auxiliary relay for reverse phase protector
K12,13,14,15A .
Auxiliary relay for fan speed control
KP.................. Pumpcontactor (field supply)
L1,L2,L3 ........ Live
M11~32F ....... Fan motor
M1,2,3C ........ compressor motor
N.................... Neutral
PE .................. Main earth terminal
Q1,2,3D ......... Discharge thermal protector
Q11~32F........ Fan thermal protector
R1P ............... Reverse phase protector
R3T ............... Sensor for ambient temperature measurement
R4,5,6T ......... Outlet water temperature sensor
R7T ............... Sensor for evaporator inlet water temperature
measurement
S1,2,3HP ....... High pressure switch
S1,2,3LP ....... Low pressure switch
S8S ............... Switch for dual setpoint (field supply)
S9S ............... Switch for remote start/stop (field supply)
S10L .............. Flowswitch (field supply)
S11L .............. Contact that closes if the pump is working (field supply)
S12S ............. Main isolator switch (field supply)
TR1 ............... Transfo 230V 24V (30VA) for power supply of
controllers
TR2 ............... Transfo 24V 24V (10VA)
X*A,X*B ........ Interconnection connector switchbox 1, switchbox 2
X*A,X*C ........ Interconnection connector switchbox 1, switchbox 3
X*B,X*C ........ Interconnection connector switchbox 2, switchbox 3