Troubleshooting ESiE04-03
3–34 Part 3 – Troubleshooting
3
1
3
4
5
Loading
parameters
To load parameters when you have entered the factory menu, proceed as follows:
To exit the factory
menu
To exit the factory menu when you have changed all parameters, proceed as follows:
Step Action Result
1
Scroll using u or d to go to parameter HC.
2
Press
s.
3
Scroll using
u or d to change the value to 01.
4
Press s.
You see parameter HC.
5
Scroll using
u or d to go to parameter H1.
You can start initialization.
6
Press
s.
7
Scroll using
u or d to change the value to 03.
8
Press
s.
You see parameter H1.
9
Use
u or d to go to the other parameters.
For the other parameters, see the tables further in this sec-
tion:
Sensors
Regulator
Compressor
Fans
Anti-freeze and supporting heaters
Alarm
Others.
Step Action
1
Press p.
2 Turn OFF the power supply.