ESiE04-03 Troubleshooting
Part 3 – Troubleshooting 3–35
33
4
5
1
Sensors The table below contains the settings of the sensors.
Regulator The table below contains the settings of the regulator.
Code Parameter Function EUWY*5-24KAZW1
Read/
write
13 Factory Air coil or ambient probe type 1 r/w
16 Factory Offset for /1 0°C
17 Factory Offset for /2
18 Factory Offset for /3
1b Factory Digital filter 4
1v Factory Input limitation 8
1d User Measurement unit 0
Code Parameter Function
EUWY*5-
12KAZW1
EUWY*16-
24KAZW1
Read/
write
r1 Direct Cooling set point 12°C 12°C r/w
r2 Direct Cooling hysteresis 3°C 3°C
r3 Direct Heating set point 30°C 30°C
r4 Direct Heating hysteresis 3°C 3°C
r5 Factory Compressor rotation __ 0°C
ra Factory Min. cooling set point Standard 7°C 7°C
ZL option -7°C -7°C
ZH option -2°C -2°C
rb Factory Max. cooling set point 25°C 25°C
rv Factory Min. heating set point 25°C 25°C
rd Factory Max. heating set point 48°C 48°C