The Digital Controller ESiE04-03
2–32 Part 2 – Functional Description
3
1
2
4
5
(1)
: c9 and ca and cv can be reset.
(2)
: To unlock the keyboard, see "Unlocking the Keyboard" on page 3–27.
When you lock the keyboard, the following advanced functions are unavailable:
Modifying direct and user parameters (parameters can be displayed but not modified)
Selecting cooling mode
Resetting the timers.
Adjusting settings To adjust settings, see "Reading or Adjusting Parameter Settings: the Programming Procedure" on
page 2–33.
cv
(1)
Total running hours of the pump Direct Read-only Read-only
p4 Activation period of the buzzer User 1 min 1 min
0min:
buzzer
disabled
1-14 min:
buzzer
activation
period
15 min:
buzzer
activated
until
m
button is
pressed
1min
h6 Remote cool/heat User 0 0 0 or 1 1
h7 Remote start/stop User 0 0 0 or 1 1
h8 No. of terminals User 0 0 0 or 1 1
h9
(2)
Controller keyboard lock User 1 1 0: Locked
1: Unlocked
1
ha Units serial address User 1 1 1 to 199 1
hb Remote control password User 1 1 1
hg Software release version User 1.5 (Read-
only)
1.5 (Read-
only)
——
Code Description Type
Default Value
Limit values
Step
value
EUWA*5-
24KAZW1
EUWY*5-
24KAZW1