Daikin EUWAB8KAZW1 [123/215] Settings direct and user parameters

Daikin EUWAN5KAZW1 [123/215] Settings direct and user parameters
ESiE04-03 The Digital Controller
Part 2 – Functional Description 2–31
3
2
4
5
1
2.5 Settings: Direct and User Parameters
Direct and user
parameters
The table below describes the direct and user parameters.
How to access the
parameters
To access the parameters, proceed as follows:
Overview of the
parameters
The table below contains an overview of all the parameters. Each parameter is defined by a code and
a value.
Parameters Description Example
Direct Are used for the daily usage of
the unit.
To set the cooling temperature set point.
To read the operational information.
User Provide advanced features. Remote control
To access the… parameters Press 5 s on… A password is…
Direct
s
Not required.
Direct and user
p
Required. Use 22 as password.
Code Description Type
Default Value
Limit values
Step
value
EUWA*5-
24KAZW1
EUWY*5-
24KAZW1
:d Measurement unit (°C or °F) User 0°C 0°C 0 or 1 1
r1 Cooling temperature set point Standard Direct 12.0°C 12.0°C 7.0 to 25.0°C 0.1°C
ZL option -7.0 to 25.0°C
ZH option -2.0 to 25.0°C
r2 Cooling temperature difference Direct 3.0°C 3.0°C 0.3 to 19.0°C 0.1°C
r3 Heating temperature set point Standard Direct 30.0°C 25.0 to
48.0°C
0.1°C
ZL option
ZH option
r4 Heating temperature difference Direct 3.0°C 0.3 to 19°C 0.1°C
r6 Outlet water temperature Direct Read-only Read-only 0.1
c7 Time delay between the pump start-up and the
compressor start-up
User 15 s 15 s 0 to 150 s 1 s
c8 Time delay between the pump shutdown and the
compressor shutdown
User 0min 0min
c9
(1)
Total running hours of the
compressor 1
Direct Read-only Read-only 1 h
ca
(1)
Total running hours of the
compressor 2
Direct Read-only Read-only 1 h
cb Maintenance threshold of c9 User 0 (Read-
only)
0 (Read-
only)
0 to 10000 h 100 h