Daikin EUWAB10KAZW1 [90/215] Wiring diagram euwa 5 24kazw1 and euwy 5 24kazw1

Daikin EUWAB5KAZW1 [90/215] Wiring diagram euwa 5 24kazw1 and euwy 5 24kazw1
Wiring Layout ESiE04-03
1–80 Part 1 – System Outline
3
11
4
5
3.5 Wiring Diagram: EUWA*5-24KAZW1 and EUWY*5-24KAZW1
Diagram
Option: OP10
Only for units
with buffertank
For AC5-12
For AC16-24
Only for units with integrated pump
Option kit: EKAC10B
to microchiller compact
Addres card
serial line
to gateway
to
cable
shield
Option kit: EKRUMC
Remote
user
interface
Only for
AC16-24 heatpump
Only for
AC5-24 heatpump
Only for AC16-24
Defrost temp
S2A
Only for AC16-24
Option kit:
EKSS16/24K
Option kit:
EKSS 5/12K
Only for AC16-24
Units with integrated pump (400V)
Units without integrated pump (400V)
Fuses
Fuses
All models (400V)
Fuses +
overcurrent
(St. pump)
(OP pump high)
(OP ZH/ZL)
(OP pump high
+ OP ZH/ZL)
For AC5
Digital inputs
DI1 Reverse phase detection (L1-N)
DI2 Reverse phase detection (N-L3)
DI3 M1C ON detection
DI4 M2C ON detection
DI5 Safety device detection
DI6 Pump ON detection
DI7 --
DI8 --
DI9 --
DI10 Reverse valve request
Digital outputs (relays)
RY1 Reve rsed phase protector
RY3 Pump/general operation
RY4-24 Fan speed relay 1
RY5-25 Fan speed relay 2
RY6 Heater tape
RY7 Reve rsing valve circ1
RY8 Reversing valve circ2
RY9 M1C off (during defros
t)
RY10 M2C off (during defrost)
RY12-22 Fan speed relay 3
RY27 reversing valve of water circuit
Others
HAP light emitting diode (service monitor green)
H1P, H2P light emitting diode (service monitor red)
S1A dipswitch (unit setting)
S2A dipswitch (defr. & fan setting)
Digital inputs
X1 (ID1-GND) : flow switch
X1 (ID2-GND) : Remote C/H selection
X1 (ID3-GND) : high pressure switch +
discharge protector +
overcurrent
X1 (ID4-GND) : low pressure switch
X1 (ID5-GND) : remote On/Off
Digital outputs relays
X2 (C1/2-NO1) : compressor M1C on
X2 (C1/2-NO2) : compressor M2C on
X2 (C3/4-NO
3) : voltage free contact
for pump
X2 (C3/4-NO4) : reversing valve
X2 (C5-NO5) : alarm voltage free
contact
Analog inputs
X1 (B1-GND) : inlet water t°
X1 (B2-GND) : outlet water t°
X1 (B3-GND) : none
Analog outputs
X1 (Y-GND) :