ESIE11-05 Test Run
Commissioning and Test Run 207
1.2.3 Onsite Settings
Notes In the case of a EW*Q040BA, EW*Q050BA, EW*Q064BA, all onsite settings should be made
on the master unit. Settings made on sub units are invalid.
The outdoor unit to which is next to the hydrobox is the master unit, and the other unit is the
slave.
Onsite settings
with the power on
Use the BS button switches (BS1 through BS5) on the outdoor
unit PCB (A1P) to make the necessary onsite settings.
See the “Service Precautions” label on the EL. COMPO. BOX lid
for details on the positions and operating method of the BS button
switches and on the onsite setting.
Make sure to record the setting on the accessory “REQUEST
FOR THE INDICATION” label.
Warning
Electric Shock Warning
Use an insulated rod to operate the BS buttons via the inspection door of EL. COMPO. BOX lid.
There is a risk of electric shock if you touch any live parts, since this operation must be
performed with the power on.
1.2.4 Test Run
Before test run Make sure the following works are completed in accordance with the installation manual.
Piping work
Wiring work
Test run After check operation is completed, operate the unit normally and check the following.
1. Make sure the unit is operating normally.
2. Check to see if cold (or hot) water is coming out from the hydrobox.
3. Close unit with all service panels, the service panels of the switch box should only be
opened by a licensed electrician for maintenance purposes.
Notes If a knocking sound can be heard in the liquid compression of the compressor, stop the unit
immediately and then energize the crank case heater for a sufficient length of time before
restarting the operation.
Once stopping, the compressor will not restart in about 3 minutes even if the On/Off button
of the remote controller is pushed.
The outdoor unit fan may rotate at low speeds if the Night-time low noise setting or the
External low noise level setting is made, but this is not a malfunction.
Inspection
door
[Service Precautions]
label
EL.COMPO.
BOX lid