Daikin EWYQ025BAWP [102/223] Automatic temperature compensation

Daikin EWYQ021BAWP [102/223] Automatic temperature compensation
ESIE11-05 Remote Controller
Functional Description 91
8.2.9 [8] Option Setup
[8-00] Remote controller temperature control
[8-00]=0 the unit operates in leaving water temperature control. This the default setting.
[8-00]=1 the unit operates in room temperature control. This means that the remote
controller is used as room thermostat, so the remote controller can be placed in the living
room to control the room temperature.
[8-01] Setting not available
[8-03] Quiet mode
The unit has a quiet mode functionality for which 3 levels can be selected:
[8-03]=1 low noise level 1 (default)
[8-03]=2 low noise level 2
[8-03]=3 low noise level 3
Activating this quiet mode is done by pushing the QUIET MODE button on the remote
controller or through the schedule timer.
[8-04] Freeze-up prevention
The unit has a freeze-up prevention functionality for which 3 levels can be selected:
[8-04]=0 prevention level 0 (default: no prevention)
[8-04]=1 prevention level 1
[8-04]=2 prevention level 2
Prevention level 0 (0)
- no prevention (default)
Prevention level 1 (1)
- If Tamb <4°C & EWT or LWT <7°C
pump starts
- If EWT or LWT <5°C for 5 minutes
unit starts
Prevention level 2 (2)
-If Tamb <4°C
pump starts
- If EWT or LWT <5°C for 5 minutes
unit starts
It is advised to enable freeze-up prevention if the indoor unit is located in a colder ambient
room (e.g. garage, ...) to prevent water freeze-up.
8.2.10 [9] Automatic Temperature Compensation
If needed, it is possible to adjust some thermistor value of the unit by a correction value. This
can be used as countermeasure for thermistor tolerances or capacity shortage.
The compensated temperature (= measured temperature plus compensation value) is then
used for controlling the system and will be displayed in the temperature read-out mode.
[9-00] Leaving water temperature compensation value for heating operation.
[9-01] Leaving water thermistor auto corrective function. When enabled, this function will
take into account the outdoor ambient conditions and correct the measured value which will
be used for the logic.
E.g. when the ambient temperature is high during cooling mode, the logic will correct the
measured value of the leaving water thermistor to a lower value to take into account
influence of high ambient temperatures in the measurement.
[9-02] Setting is not applicable.
[9-03] Leaving water temperature compensation value for cooling operation. Not available
for heating only model.
[9-04] Setting is not applicable.